Manual
    <6.  Explanation of Basic Items>
6-7
IM 01C25T04-01EN
6.4.2  Target Mode
The Target modes permitted for the AI function 
block are Automatic (Auto), Manual (Man), and 
Out of Service (O/S). When the Target mode of PB 
(Physical Block) is Out of Service (O/S), Actual is 
Out of Service (O/S) even if Automatic (Auto) or 
Manual (Man) is written to Target.
6.4.3  Basic Parameter of AI function block
Output Value (OUT)
The function block parameter OUT contains the 
current measurement value in a vendor specic 
or conguration adjusted engineering unit and the 
belonging status in Auto Mode. Also contains the 
value and status set by an operator in Man Mode.
Simulation (SIMULATE)
Simulation parameter is to simulation mainly for 
checking arbitrarily set the value and input status 
from SENSROR Transducer block.
PV Scale (PV_SCALE)
Conversion of the process variable into percent 
using the high and low scale values.
Linearization type (LIN_TYPE)
Linearization type of output signal can be select 
from Linear or Square root. Linearization type of 
AI function block can apply to have different output 
mode for display and output signal. (For example, 
Display mode: Square root, Output mode: Linear)
Out Scale (OUT_SCALE)
Scale of the process variable. This parameter 
contains the values of the lower limit and upper limit 
effective range, the code number of the engineering 
unit of process variable and the useful number of 
digits on the right hand side of the decimal point.
Filter Time Const (PV_FTIME)
Damping time of the process variable. 
Fail Safe Mode (FSAFE_TYPE)
Fail Safe Mode is parameter used to dene the 
reaction of the device, if a BAD status of signal to 
AI function block (OUT.Status and OUT.Value) is 
detected. This is available only when Target Mode 
of AI function block is in “Auto”. Refer to 5.4.1 for 
conguration.
Table 6.2  Fail Safe Mode (Classic Status)
Fail Safe Mode Output Value and Status (Quality)
Default value is 
used as output 
value
value Fail Safe Default value
Status UNCERTAIN - Substitute Value
Storing last valid 
output value
value Last stored valid OUT value
Status UNCERTAIN - Last Usable Value
The calculated 
output value is 
incorrect
value wrong calculated value
Status  BAD - *(* as calculated)
Table 6.3  Fail Safe Mode (Condensed Status)
Fail Safe Mode Output Value and Status (Quality)
Default value is 
used as output 
value
value Fail Safe Default value
Status BAD - Passivated, Constant *
1
UNCERTAIN - Substitute Set *
2
UNCERTAIN - Process Related *
3
UNCERTAIN - Substitute Set *
4
Storing last valid 
output value
value Last stored valid OUT value
Status BAD - Passivated, Constant *
1
UNCERTAIN - Substitute Set *
2
UNCERTAIN - Process Related *
3
UNCERTAIN - Substitute Set *
4
The calculated 
output value is 
incorrect
value wrong calculated value
Status BAD - Passivated, Constant *
1
BAD - Maintenance Alarm *
2
BAD - Process Related *
3
BAD -Function Check *
4
*1:  When input status = BAD - Passivated
*2:  When input status = BAD - Maintenance Alarm
*3:  When input status = BAD - Process Related
*4:  When input status = BAD - Function Check
6.5  Totalizer Function Block
6.5.1  Functional Block
The Totalizer function block, incorporates 
analog signal from SENSOR transducer block, 
performs integrate a rate or another quantity to 
the corresponding integral. And also, this function 
block can be tailored for different applications or 
determines the fail-safe behavior.
6.5.2  Target Mode
The Target Mode permitted for the Totalizer function 
block are Automatic (Auto), Manual (Man), and Out 
of Service (O/S).