    <5.  Parameter Setting>
5-10
IM 01C25T04-01EN
5.4  Output Signal Setup
5.4.1  Fail Safe Mode
Fail Safe Mode denes the Output Value and 
Status (Quality) when status of input signal to AI 
function block or Totalizer function block is BAD. 
This function is valid only when Actual Mode of 
AI function block or Totalizer function block is in 
“AUTO”
•  Procedure to call up the display  
(AI function block)
DTM Output → Analog Input (1-3) → Fail Safe 
Mode
EDD Output → Function Block (1-3) – Analog 
Input → Fail Safe Mode → Fail Safe 
Mode
•  Procedure to call up the display  
(Totalizer function block)
DTM Output → Totalizer → Fail Safe Mode
EDD Output → Function Block 4 – Totalizer → 
Fail Safe Mode
5.4.2  Channel
Channel is the parameter to select the signal which 
is calculated in SENSOR Transducer Block. Target 
Mode of each Function Block need to be changed 
to Out of Service (O/S).
DTM Output → Analog Input (1-3), Totalizer → 
Target Mode 
EDD Output → Function Block (1-3) – Analog 
Input, Function Block 4 - Totalizer → 
Target Mode
•  Procedure to call up the display
DTM Output → Analog Input (1-3), 
Totalizer → Channel →
EDD Output → Function Block (1-3) 
– Analog Input, Function Block 4 - 
Totalizer → Channel →
→ Pressure Value Row pressure value before 
scaling
→ Primary Value Differential pressure value
→ Calculated Value Calculated value
→ Static Pressure 
(H)
Static pressure value of high 
pressure side
→ Static Pressure 
(L)
Static pressure value of low 
pressure side
→ Capsule 
Temperature
Capsule temperature value
→ Amplier 
Temperature
Amplier temperature value
5.4.3  Totalizer
This section shows procedure to set Signal Totalizer 
function. Refer to subsection 5.4.2 for Channel 
setting of Totalizer Function Block. Follow below 
procedure to set signal totalizer function. 
<1> Set Totalizer Value Set
•  Procedure to call up the display
DTM Output → Totalizer → Totalizer 
Value Set →
EDD Output → Function Block 4 – 
Totalizer → Totalizer Value →
→ Totalize Normal operation of the totalizer
→ Reset Assign value 0 to totalizer
→ Preset Assign value of present value to 
totalizer
<2> Set Mode
•  Procedure to call up the display
DTM Output → Totalizer → Mode →
EDD Output → Function Block 4 – 
Totalizer → Mode →
→ Pos. and neg. 
value
True arithmetic integration of the 
incoming rate values
→ Positive value 
only
Totalization of positive incoming 
rate value only
→ Negative value 
only
Totalization of negative incoming 
rate value only
→ Hold Count Totalization stopped