    <5.  Parameter Setting>
5-6
IM 01C25T04-01EN
5.3.3  Signal Characterizer
Below is the example of performing the signal 
characterizer as shown in Figure 5.2. Target Mode 
of Sensor Transducer Block need to be changed 
to Out of Service (O/S) before setting linearization 
table. In order to use signal characterizer, 
“User dened (table)” must be chosen for 
Characterization Type. Refer to subsection 5.1.3 for 
changing Characterization Type.
40% 100%0%
20%
100%
Y
X
F0504.ai
Figure 5.2
<1> Conguration of new linearization table can be 
performed in “Query Device” in “Device” menu 
in top section of tool window.
•  Procedure to call up the display
DTM [Device] → Conguration → 
Characterization → Table 
Coordinate →
EDD [Device] → Characterization → 
Linearization →
→ Operation Mode Select the transaction of the user 
dened table
Table 5.1  Operation Mode
Code Description
0 Not initialized.
1 New operation characteristic, rst value.
3 Last value, end of transmission, check table, or 
swap the old curve with the new curve.
4 Delete point of table.
5 Insert point dened.
6 Replace point of table.
Select “1: New operation characteristic, rst value” 
for new operation.
<2> Enter Lower and Upper Scale In / Out value.
  Refer to subsection 5.1.2 and 5.3.2 for 
procedure. For this case, scales should be 
entered shown as below.
Scale In: Lower Value → 0
Scale In: Upper Value → 100
Scale out: Lower Value → 0
Scale unt: Upper Calue → 100
<3> Enter Coordinate No. and X, Y value
•  Procedure to call up the display
DTM [Device] → Conguration → 
Characterization → Table 
Coordinate → 
EDD [Device] → Characterization → 
Linearization →
→ Coordinate No. Number of coordinate
→ X Y value couple 
- X
Input value of linearization table
→ X Y value couple 
- Y
Output value of linearization table
X_
i
=(PrV–ScaleIn_L)/(ScaleIn_U–ScaleIn_L)
Y_
i
=X_
i
×{(ScaleOut_U–ScaleOut_L)+ScaleOut_L}
(i=1 to 31)
PrV: Pressure Value
ScaleIn_L: Scale In:Lower Value 
ScaleIn_U: Scale In:Upper Value
ScaleOut_L: Scale Out:Lower Value 
ScaleOut_U: Scale Out:Upper Value
For this case, Coordinate No. and X/ Y values 
should be entered shown as below.
Coordinate No.: 1
X Y value couple – X : 0.0
X Y value couple – Y : 0.0
Coordinate No.: 2
X Y value couple – X : 0.4
X Y value couple – Y : 0.2
Coordinate No.: 3
X Y value couple – X : 1.0
X Y value couple – Y : 1.0
<4> To denite linearization table, select Code: 3 in 
Operation Mode shown in procedure <1> and 
update linearization table.