<5. Parameter Setting>
5-6
IM 01C25T04-01EN
5.3.3 Signal Characterizer
Below is the example of performing the signal
characterizer as shown in Figure 5.2. Target Mode
of Sensor Transducer Block need to be changed
to Out of Service (O/S) before setting linearization
table. In order to use signal characterizer,
“User dened (table)must be chosen for
Characterization Type. Refer to subsection 5.1.3 for
changing Characterization Type.
40% 100%0%
20%
100%
Y
X
F0504.ai
Figure 5.2
<1> Conguration of new linearization table can be
performed in “Query Device” in “Device menu
in top section of tool window.
Procedure to call up the display
DTM [Device] Conguration
Characterization Table
Coordinate
EDD [Device] Characterization
Linearization
Operation Mode Select the transaction of the user
dened table
Table 5.1 Operation Mode
Code Description
0 Not initialized.
1 New operation characteristic, rst value.
3 Last value, end of transmission, check table, or
swap the old curve with the new curve.
4 Delete point of table.
5 Insert point dened.
6 Replace point of table.
Select “1: New operation characteristic, rst value
for new operation.
<2> Enter Lower and Upper Scale In / Out value.
Refer to subsection 5.1.2 and 5.3.2 for
procedure. For this case, scales should be
entered shown as below.
Scale In: Lower Value 0
Scale In: Upper Value 100
Scale out: Lower Value 0
Scale unt: Upper Calue 100
<3> Enter Coordinate No. and X, Y value
Procedure to call up the display
DTM [Device] Conguration
Characterization Table
Coordinate
EDD [Device] Characterization
Linearization
Coordinate No. Number of coordinate
X Y value couple
- X
Input value of linearization table
X Y value couple
- Y
Output value of linearization table
X_
i
=(PrV–ScaleIn_L)/(ScaleIn_U–ScaleIn_L)
Y_
i
=X_
i
×{(ScaleOut_U–ScaleOut_L)+ScaleOut_L}
(i=1 to 31)
PrV: Pressure Value
ScaleIn_L: Scale In:Lower Value
ScaleIn_U: Scale In:Upper Value
ScaleOut_L: Scale Out:Lower Value
ScaleOut_U: Scale Out:Upper Value
For this case, Coordinate No. and X/ Y values
should be entered shown as below.
Coordinate No.: 1
X Y value couple X : 0.0
X Y value couple Y : 0.0
Coordinate No.: 2
X Y value couple X : 0.4
X Y value couple Y : 0.2
Coordinate No.: 3
X Y value couple X : 1.0
X Y value couple Y : 1.0
<4> To denite linearization table, select Code: 3 in
Operation Mode shown in procedure <1> and
update linearization table.