Manual
    <4.  Getting Started>
4-4
IM 01C25T04-01EN
4.5  Integration of GSD le and 
IDENT Number
The GSD le and Ident number are necessary 
for PROFIBUS communication. Before starting 
communication, the device must be specied by the 
GSD le in the host system and the Ident number of 
the device.
The PROFIBUS device has a prole Ident number 
and a device-specic Ident number. There are GSD 
les which correspond to each number. The prole 
GSD le is a general-purpose le which is dened 
by the kind and number of function blocks of the 
device. This le helps improve the compatibility 
among devices.
By setting the PROFIBUS Ident Number (IDENT_
NUMBER_SELECTOR) parameter of the physical 
block or the Ident number at the Local Operation 
Interface, the Ident number will be linked with the 
corresponding GSD le. For the setting at the Local 
Operation Interface, see Chapter 7.5.
Table 4.3  Device specic ID GSD le
Model Name
Device specic 
Ident Number
Device Specic 
GSD le
EJXA
0x4581 YEC4581.gsd
EJAE
0x4580 YEC4580.gsd
Table 4.4  Prole ID GSD le
Prole ID
Prole Ident 
Number
Prole GSD le
AI ×1 0x9700 pa139700.gsd
AI ×2 0x9701 pa139701.gsd
AI ×3 0x9702 pa139702.gsd
AI ×1+TOT 0x9740 pa139740.gsd
AI ×2+TOT 0x9741 pa139741.gsd
AI ×3+TOT 0x9742 pa139742.gsd
4.6  Bus Address Setup
This section describes the procedure to set 
Bus Address in the transmitter. Every device in 
PROFIBUS must be assigned a unique address 
in the range of 0(0x00) to 126(0x7e). If it is not 
specied at the time of order, 126(0x7e) is the 
factory default. Do not change to 0, 1 or 2 as these 
are used by master devices. 
There are two ways to set Bus Address: by using 
communication tools or by Local Operation 
Interface. Refer to chapter 7.5 for setting procedure 
by using Local Operation Interface. Below is an 
example of changing Bus Address from 5 to 20 by 
using DTM works.
1.  In the FieldMate window, click [Segment 
Viewer] → [User Dened Connection] and click 
[New FDT Project ...].
2.  In the DTM Works window, click [Topology] → 
[Add].
3.  In the Catalog window, click [PROFIBUS DPV1] 
of Protocol → [PROFIdtm DPV1] and click 
[Add] button.
4.  In the DTM Works window, click [Device] → 
[Connect].
5.  In the DTM Works window, click [Device] → 
[Additional Functions] → [Set Device Station 
Address...].
6.  Enter [Old Address] to 5 and [New Address] to 
20 and click [Set] button. 
“New address successfully set” is displayed in 
the State eld.
7.  Click [Close] button and exit DTM works
8.  When changing a parameter after changing 
the Address, click [View] → [Update] in the 
FieldMate window.