Manual
    <4.  Getting Started>
4-3
IM 01C25T04-01EN
(3)  Ident Number
Refer to section 4.5 for explanation of Ident 
Number.
(a)  Conrmation by the name plate
Device specic Ident Number and Prole Ident 
number is marked on the name plate. Prole 
Ident Number is inside [ ]. (9700 to 02(9720), 
9740 to 42(9742))
Refer to Figure 4.3. 
(b)  Conrmation from integral indicator (When the 
integral indicator code “E”)
Please refer to section 4.2.
(c) Conrmation by parameter
Ident Number can be conrmed from Physical 
Block parameter Ident Number (IDENT_
NUMBER).
•  Procedure to call up the display
DTM Physical Block → Identication → ID No.
EDD Identication → Device → ID No.
F0404.ai
SW: X.XX [ X . . . X ]
Device Revision
Device Revision Compatibility
Software Revision
ID: XXXX [ 9700-02, 9740-42 ]
Profile Ident Number
Device Specific Ident Number
(EJX: 4581 EJA: 4580)
Figure 4.3  Name Plate
4.4  Master Settings
To activate PROFIBUS PA, the following bus 
parameters must be set for the master.
Table 4.2  Bus Parameters
Symbol  Parameter
Description and 
Settings
Transmission 
rate
Transmission 
Rate
The transmission rate of 
PROFIBUS PA matches 
that of the segment 
coupler.
e.g P+F: 93.75 kbps, 
Siemens: 45.45 kbps
TSL Slot Time The maximum time a 
master station must 
wait for the complete 
reception of the rst 
octet of a response (11 
bits).
e.g: 4095
min TSDR Min. Station 
Delay Timer
Sets the minimum time 
at which a slave can 
send the rst bit of a 
response back.
max TSDR Max. Station 
Delay Time
Sets the maximum time 
at which a slave can 
send the rst bit of a 
response back.
TQUI Quiet Time Controls the time at 
which the bus electronics 
or software of the sender 
is set to receive mode 
after a message is sent.
TSET Setup Time Sets the maximum 
allowable time for 
parameter setting and 
response by the slave.
HSA Highest 
Station 
Address
Sets the highest station 
address in the network.
G Gap update
factor
Sets the number of 
token cycles after which 
the master will search for 
a new master.
max. retry
limit
Max Retry
Limit
Sets the number 
of retries that are 
performed after a 
receiver does not 
respond to a message.