Note 6. Installation Instructions
Non-Hazardous Location
Hazardous Location
F0202.ai
Terminator
Safety Barrier
Transmitter
Pressure
Transmitter
Transmitter
+
−
+
−
+
−
Terminator
+
−
+
−
[Installation Diagram]
SUPPLY
•  In the rating 1(*1), the output current of the 
barrier must be limited by a resistor ‘Ra’ such 
that Io = Uo/Ra.
•  In the rating 2(*2), the output of the barrier 
must be the characteristics of the trapezoid 
or the rectangle and this transmitter can be 
connected to Fieldbus equipment which are 
in according to the FISCO model.
•  The terminators may be built in by a barrier.
•  More than one transmitter may be connected 
to the power supply line.
•  The terminator and the safety barrier shall be 
certied.
Electrical data:
Maximum Input Voltage Ui: 24 V
Maximum Input Current Ii: 250 mA
Maximum Input Power Pi: 1.2 W
Maximum Internal Capacitance Ci: 3.52 nF
Maximum Internal Inductance Li: 0 μH
*1:
Rating 1
or
Maximum Input Voltage Ui: 17.5 V
Maximum Input Current Ii: 380 mA
Maximum Input Power Pi: 5.32 W
Maximum Internal Capacitance Ci: 3.52 nF
Maximum Internal Inductance Li: 0 μH
or
Maximum Input Voltage Ui: 17.5 V
Maximum Input Current Ii: 460 mA
Maximum Input Power Pi: 5.32 W
Maximum Internal Capacitance Ci: 3.52 nF
Maximum Internal Inductance Li: 0 μH
*2:
Rating 2
c.   ATEX Intrinsically Safe Ex ic
Caution for ATEX Intrinsically safe Ex ic
The transmitters with option code /KN26 for 
potentially explosive atmospheres:
•  Applicable Standard:
  EN 60079-0:2009/EN 60079-0:2012, 
EN 60079-11:2012
•  Type of Protection and Marking Code: 
II 3G Ex ic IIC T4 Gc
•  Ambient Temperature: –30* to +60°C
  * –15°C when /HE is specied.
•  Maximum Process Temperature: 120°C
•  Ambient Humidity: 
0 to 100% (No condensation)
•  IP Code: IP66
•  Ambient pollution degree: 2
•  Overvoltage category: I
Note 1. Electrical Data
  Ui = 32 V
  Ci = 3.52 nF
  Li = 0 µH
Note 2.  Installation
•  All wiring shall comply with local installation 
requirements. (refer to the control drawing)
•  When installing the transmitter in “ic” 
FISCO system or FNICO system, follow the 
installation requirements of each system.
•  Cable glands, adapters and/or blanking 
elements shall be of Ex “n”, Ex “e” or Ex “d” 
and shall be installed so as to maintain the 
specied degree of protection (IP Code) of 
the transmitters.
Note 3. Maintenance and Repair
•  The instrument modication or parts 
replacement by other than authorized 
representative of Yokogawa Electric 
Corporation is prohibited and will void ATEX 
intrinsically safe.
Associated 
Apparatus
Transmitter
Nonhazardous Area
[Control drawing]
Hazardous Area
+ 
– 
F0203.ai
•  Above drawing shows the installation of 
Entity system.
  When installing the transmitters in “ic” 
FISCO system or FNICO system, follow the 
installation requirements of each system.