Manual

<2. Handling Cautions>
2-2
IM 01C25T04-01EN
2.1.2 CSA Certication
a. CSA Explosionproof Type
Caution for CSA explosionproof type.
Note 1. The transmitters with optional code /CF1
are applicable for use in hazardous
locations:
Certicate: 2014354
Applicable Standard:
C22.2 No.0, C22.2 No.0.4, C22.2 No.0.5,
C22.2 No.25, C22.2 No.30, 22.2 No.94,
C22.2 No.61010-1-04, C22.2 No.60079-0,
C22.2 No.60079-1
Explosion-proof for Class I, Groups B, C and
D.
Dustignition-proof for Class II/III, Groups E, F
and G.
Enclosure: NEMA 4X, IP66/IP67
Temperature Code: T6...T4
Ex d IIC T6...T4
Enclosure: IP66 and IP67
Maximum Process Temperature:
12C (T4), 100°C (T5), 85°C (T6)
Ambient Temperature:
–50* to 75°C (T4), –50* to 80°C (T5),
–50* to 75°C (T6)
* –15°C when /HE is specied.
Supply Voltage: 32 V dc max.
Output Signal: 15 mA dc
Note 2. Wiring
All wiring shall comply with Canadian
Electrical Code Part I and Local Electrical
Codes.
In hazardous location, wiring shall be in
conduit as shown in the gure.
WARNING:
A SEAL SHALL BE INSTALLED WITHIN
50cm OF THE ENCLOSURE.
UN SCELLEMENT DOIT ÊTRE INSTAL À
MOINS DE 50cm DU BOÎTIER.
WARNING:
WHEN INSTALLED IN CL.I, DIV 2, SEAL
NOT REQUIRED.
UNE FOIS INSTALLÉ DANS CL I, DIV 2,
AUCUN JOINT N'EST REQUIS.
Note 3. Operation
WARNING:
AFTER DE-ENERGIZING, DELAY 5
MINUTES BEFORE OPENING.
APS POWER-OFF, ATTENDRE 5
MINUTES AVANT D'OUVRIR.
WARNING:
WHEN AMBIENT TEMPERATURE 65°C,
USE THE HEAT-RESISTING CABLES
90°C.
QUAND LA TEMPÉRATURE AMBIANTE
65°C, UTILISEZ DES CÂBLES
SISTANTES Á LA CHALEUR 9C.
Take care not to generate mechanical
sparking when accessing to the instrument
and peripheral devices in a hazardous
location.
Note 4. Maintenance and Repair
The instrument modication or parts
replacement by other than authorized
representative of Yokogawa Electric
Corporation and Yokogawa Corporation of
America is prohibited and will void Canadian
Standards Explosionproof Certication.
Non-hazardous
Location
Equipment
32 V DC Max.
15 mA DC
Signal
Non-Hazardous
Locations
Hazardous Locations Division 1
Non-Hazardous
Locations
Hazardous Locations Division 2
50 cm Max.
Sealing Fitting
Conduit
Non-hazardous
Location
Equipment
32 V DC Max.
15 mA DC
Signal
Sealing Fitting
SUPPLY
PULSE
CHECK
ALARM
Transmitters
SUPPLY
PULSE
CHECK
ALARM
Transmitters
F0201.ai