Instruction Manual
IM 01C21F01-01E
8-16
8. BRAIN TERMINAL BT200 OPERATION
8.4 Displaying Data Using the
BT200
8.4.1 Displaying Measured Data
The BT200 can be used to display measured data.
The measured data is updated automatically every 7
seconds. In addition, the display can be updated to
the present data value at any time by pressing the 
(DATA) key. For parameters associated with the
display of measured data, see Subsection 8.3.1,
“Parameter Summary.”
• Example: Display output.
DATA DIAG PRNT ESC
PARAM
 A10:OUTPUT (%)
 A11:ENGR.OUTPUT
 A20:AMP TEMP
HOME SET ADJ ESC
MENU
 A:DISPLAY
 B:SENSOR TYPE
F0834.EPS
Data is updated automatically 
at 7-second intervals.
Display “A10: OUTPUT (%).”
PARAM
 A10:OUTPUT (%)
 XX.X %
 A11:ENGR.OUTPUT
 YY.Y %
 A20:AMP TEMP
 ZZ deg C
communi
8.4.2 Display Transmitter Model and
Specifications
The BT200 can be used to display the model and
specifications of the transmitter.
• Example: View transmitter model name.
HOME SET ADJ ESC
MENU
 A:DISPLAY
 B:SENSOR TYPE
DATA DIAG PRNT ESC
PARAM
 B10:MODEL
 EJA510A-DC
 B11:STYLE NO.
 S1.01
 B20:LRL
 – 98.07 kPa
For the associated 
parameters, see Subsection 
8.3.1, “Parameter Summary.” 
Press .
F0835.EPS
8.5 Self-Diagnostics
8.5.1 Checking for Problems
(1) Identifying Problems with BT200
The following four areas can be checked.
        (a) Whether connections are good.
        (b) Whether BT200 was properly operated.
        (c) Whether settings were properly entered.
        (d) History of the errors.
See examples below.
• Example 1: Connection errors
ESC
communication error
Press the key. 
When the panel shown on the left 
appears, press the key.
Since communications will be 
unsuccessful if there is a problem 
in the connection to the BT200, the 
display at the left will appear. 
Recheck the connection.
Press the (OK) key.
––WELCOME––
BRAIN TERMINAL 
 ID: BT200
check connection 
push ENTER key
UTIL FEED
• Example 2: Setting entry errors
F0836.EPS
The initial data panel shows the 
result of current transmitter 
diagnostics.
DATA DIAG PRNT ESC
PARAM
 C20:PRESS UNIT
 kPa
 C21:LOW RANGE
 600 kPa
 C22:HIGH RANGE
 600 kPa
FEED PRNT ESC
DIAG
 C60:SELF CHECK
 ERROR
 < ERROR >
 < ILLEGAL LRV >
Press the (DIAG) key in the 
parameter panel to go to the 
diagnostics panel 
(C60: SELF CHECK).
An error message is displayed 
when an error occurs in the 
diagnostics panel.
OK
PARAM
 01:MODEL
 EJA510A-DC
 02:TAG NO.
 YOKOGAWA
 03:SELF CHECK
 ERROR