Instruction Manual
IM 01C21F01-01E
8-10
8. BRAIN TERMINAL BT200 OPERATION
(6) Integral Indicator Scale Setup
The following 5 displays are available for integral indicators.
T0808.EPS
D20: DISP SELECT Display Related Parameters
NORMAL %
USER SET
USER & %
INP PRES
PRES & %
Indicates –5 to 110% 
range depending on the 
Measurement range 
(C21, C22).
Indicates values depending 
on the Engineering range 
(D22, D23). 
(Note 1) 
Units set using Engineering 
unit (D21) are not indicated.
Indicates user set and % 
alternately in 3 second 
intervals.
Indicates input 
pressure. 
(Note 2) 
Indication limits –19999 
to 19999.
Indicates input pressure 
and % alternately in 3 
second intervals.
A10:OUTPUT (%)
45.6 %
Description
A11:ENGR.OUTPUT
20.0 M
A10:OUTPUT (%)
45.6 %
A11:ENGR. OUTPUT
20.0 M
A40:INPUT
456 kPa
A10:OUTPUT (%)
45.6 %
A40:INPUT
456 kPa
(Note 1) Scale range can be specified with range limit specifications up to 5 digits (excluding any 
decimal point) for low or high range limits within the range of –19999 to 19999.
The range with decimals is available to the third decimal place.
(Note 2) It indicates the value after zeroing.
See (a.) through (c.) for each setting procedure.
% indication and input 
pressure indication
Transmitter is set 
for “% display” when 
shipped.
D20: DISP SELECT
 NORMAL %
 INP PRES
 PRES & %
User-set engineering unit display
D20: DISP SELECT
 USER SET
 USER & %
D21: DISP UNIT
D22: DISP LRV
D23: DISP HRV
Set for user-set 
engineering unit display.
Set a unit to be 
displayed on the BT200.
For % display, set this 
parameter only.
Set a numeric value for 
engineering unit for 4 mA 
output (LRV).
Set a numeric value for 
engineering unit for 20 mA 
output (HRV).
F0818.EPS