Instruction Manual
IM 01C21F01-01E
8-4
8. BRAIN TERMINAL BT200 OPERATION
8.3 Setting Parameters Using the BT200
8.3.1 Parameter Summary
Instruments to which applicable:
F: Differential pressure transmitters EJA110A, EJA120A, and EJA130A
P: Pressure transmitters EJA310A, EJA430A, EJA440A, EJA510A, and EJA530A
L: Liquid level transmitters EJA210A and EJA220A
No. Description
Model+capsule type
Tag number
Applica-
bility
PLF
01
02
T0805.EPS
Rewrita-
bility
16 alphanumerics
GOOD/ERROR
Remarks
Item
MODEL
TAG NO.
Self-diagnostic result
—
—
—
03 SELF CHECK
Measured data displayA
–5 to 110%*
3
Menu nameDISPLAY
Output (in %)A10 OUTPUT (%)
–19999 to 19999Output (in engineering 
units)
A11 ENGR. 
OUTPUT
Unit specified in D30Amplifier temperatureA20 AMP TEMP
Unit specified in D30Capsule temperatureA21 CAPSULE 
TEMP
—
Sensor typeB
16 uppercase alphanumerics
Menu nameSENSOR 
TYPE
Model+spanB10 MODEL
—
Style numberB11 STYLE NO.
–32000 to 32000Lower range-limitB20 LRL
–32000 to 32000
Upper range-limitB21 URL
–32000 to 32000Minimum spanB30 MIN SPAN
—
—
—
—
—
Unit specified in D31*
1
Static pressureA30 STATIC 
PRESS
–32000 to 32000Input (indicated as the 
value after zeroing)
A40 INPUT
GOOD/ERROR, CAP MODULE FAULT, AMP MODULE FAULT, 
OUT OF RANGE, OUT OF SP RANGE*
1
, OVER TEMP (CAP),
OVER TEMP (AMP), OVER OUTPUT, OVER DISPLAY, 
ILLEGAL LRV, ILLEGAL HRV, ILLEGAL SPAN, and 
ZERO ADJ OVER
Self-diagnostic 
messages
A60 SELF CHECK
—
—
—
—
—
—
—
Maximum static 
pressure*
6
B40
Same as A60
MAX STAT.P.
Self-diagnostic 
messages
—
—
B60 SELF CHECK
Setting dataC
16 alphanumerics
Menu nameSETTING
Tag numberC10 TAG. NO.
Selected from mmH
2
O, mmAq, 
mmWG, mmHg, Torr, Pa, hPa, kPa, 
MPa, mbar, bar, gf/cm
2
, kgf/cm
2
, 
inH
2
O, inHg, ftH
2
O, psi, or atm
Measurement range
units
C20 PRESS UNIT
–32000 to 32000(but within 
measurement range)
Measurement range, 
lower range value
C21 LOW RANGE
—
Self-diagnostic 
messages
C60 Same as A60SELF CHECK
—
—
—
—
–32000 to 32000(but within 
measurement range)
Measurement range, 
higher range value
C22 HIGH 
RANGE
Selected from 0.2*
2
, 0.5, 1.0, 2.0, 
4.0, 8.0, 16.0, 32.0, or 64.0 sec.
Damping time constantC30 AMP 
DAMPING
Selected from OUT:LIN; DSP:LIN,
OUT:LIN; DSP:SQR, 
OUT:SQR; DSP:SQR
Output mode and 
integral indicator mode
C40 OUTPUT 
MODE
0.0 to 20.0%
LINEAR/ZERO
Low cutD10 LOW CUT
Low cut modeD11 LOW CUT 
MODE
NORMAL %/USER SET,
USER & %/INP PRES, PRES & %
Display selectionD20 DISP SELECT
—
Auxiliary setting data 1D Menu nameAUX SET 1
—
Default Value
As specified when ordered.
As specified when ordered.
As specified when ordered.
As specified when ordered.
2.0 s
As specified when ordered.
If not specified, 
OUT: LIN; DSP: LIN.
8 uppercase 
alphanumerics
Engineering unit for 
display
D21 DISP UNIT
10.0%
LINEAR
–5.0 to 110.0%
Lower output range-limit
D15 OUT LIMIT(L) –5.0%*
1 
–5.0 to 110.0%
Upper output range-limit
D16 OUT LIMIT(H) 110.0%
–19999 to 19999Engineering range, 
lower range value
D22 DISP LRV
–19999 to 19999Engineering range, 
higher range value
D23 DISP HRV
As specified when ordered.
As specified when ordered.
As specified when ordered.
deg C/deg FTemperature setting 
units
D30 TEMP UNIT deg C
*1: Unless otherwise specified by order. When optional code /F1 is specified, substitute the value –5 with –2.5.