<5. Parameter Summary>
5-1
IM 01C25T03-01E
5. Parameter Summary
Instruments to which applicable:
F: Differential pressure transmitters
P: Absolute and gauge pressure transmitters
L: Flange mounted differential pressure transmitters
No. Parameter name Item
*1
R/W
Content Default value
Applicable
model
Upload
data
F P L
01 MODEL Model R EJX
(for EJX series)
EJA
(for EJA series)
—
02 TAG No. Tag number R As specied
—
03 SELF CHECK Self-diagnostics R GOOD
—
A DISPLAY Measured data display
A10 OUTPUT Output (in %) R -2.5 to 110%
—
A11 PRES Measured pressure after zero
adjustment
R Unit specied in C20
—
A15 OUTPUT mA Output current R 3.600 to 21.600 mA
—
A16 ENGR. OUTPUT User scaled value R Unit specied in I30
—
A17 ENGR. EXP Exponents R Unit specied in I32
—
A20 SP % Static pressure (in %) R -10 to 110%
—
—
A21 SP Static pressure after zero
adjustment
R Unit specied in D30
—
—
A30 CAPSULE TEMP Capsule temperature R Unit specied in D40
—
A60 SELF CHECK Self-diagnostics R Refer to Table 4.1 Alarm
Message Summary
—
B SENSOR TYPE Sensor type
B10 MODEL Model and capsule type R Model and capsule type
—
B11 STYLE NO. Style number R Style number of product
—
B20 PRES LRL Lower range limit R Unit specied in C20
—
B21 PRES URL Upper range limit R Unit specied in C20
—
B22 P MIN SPAN Minimum span R Unit specied in C20
—
B30 SP LRL Lower range limit for static
pressure
R Unit specied in D30
—
—
B31 SP URL Upper range limit for static
pressure
R Unit specied in D30
—
—
B32 SP MIN SPAN Minimum span for static
pressure
R Unit specied in D30
—
—
B60 SELF CHECK Self-diagnostics R See A60
—
C BASIC SETUP Setting data
C10 TAG NO. Tag number W 16 alphanumeric characters As specied
C20 PRES UNIT Measurement range unit W mmH2O, mmAq, mmWG,
mmHg, Torr, kPa, MPa, mbar,
bar, gf/cm
2
, kgf/cm
2
, inH2O,
inHg, ftH2O, psi, atm, Pa, hPa
kPa
C21 PRES LRV Lower range value W -32000 to 32000 within
measurement range
As specied
C22 PRES URV Upper range value W -32000 to 32000 within
measurement range
As specied
C23 PRES POINT Decimal place W 0 to 4 2
C30 AMP DAMPING Damping time constant at
amplier
W 0.50(0.00) to 100.00
seconds
,
see D50
2.00 seconds or
as specied
C40 OUTPUT MODE Output mode W LINEAR or SUQARE ROOT LINEAR or as
specied
C60 SELF CHECK Self-diagnostics R See A60
—
*1: R/W: R = Read only, W = Read & Write
*2: The default value shows MWP (Maximum working pressure) of the capsule.
Since the working pressure limit varies according to the Model, refer to the General Specications section in each user’s manual.