<4. Diagnostics>
4-4
IM 01C25T01-06EN
Pressure Measurement
Operational pressure is near outside of
diagnostic range.
Even though pressure is constant, the ow
decreases than that under normal condition.
A source of pressure uctuation (pump,
compressor, blower, etc.) is shut down. As
a result, the pressureuctuation amplitude
decreases.
Level Measurement
A transmitter is used to measure tank level and
the ow of uid into or out of the tank comes to
a stop.
The agitator in the tank is shut down.
A source of pressure variation (a compressor,
etc.) that controls the internal pressure of a
sealed (closed) tank is shut down.
Before taking action in response to a blockage
alarm, consider the plant operating conditions.