<3. Parameter Setting>
3-21
IM 01C25T01-06EN
3.3.9 CPU Failure Burnout Direction and
Hardware Write Protect
There are two slide switches on the CPU assembly
board. One sets the burnout direction at CPU
failure, and the other sets a write protection function
which disables parameter changes through
the use of a handheld terminal or some other
communication method.
HIGH LOW
CPU assembly
Slide switch
Burnout direction switch
Write protection switch
Write Protection
Switch Position
Burnout Direction
Switch Position
BO H L
WR E D
H L
E D
H L
E D
H L H L
Hardware write protection switch (WR)
Burnout direction switch (BO)
Burnout Direction
Write Protection
YES
(Write disabled)
NO
(Write enabled)
F0307.ai
The parameter of AO alm typ parameter displays
the status of 4-20 mA DC output if a CPU failure
occurs. In case of a failure, communication is
disabled.
Standard specications or with option code /C3
The burnout direction switch is set toHIGH”. If a
failure occurs, the transmitter outputs a 110% or
higher signal.
With option code /C1 or /C2
The burnout direction switch is set toLOW”. If a
failure occurs, a –5% or lower output is generated.
To conrm the burnout direction at the CPU failure,
follow the procedure below.
Procedure to call up the display
DD and DTM
(excluding EJX_
HART 5[1.2])
[Root Menu] Detailed setup
→Output condition Analog
output AO alm typ
EJX_HART 5[1.2]
DTM
Conguration Analog output
AO alm typ
High Burnout direction is set to High
Low Burnout direction is set to Low
3.3.10 Software Write Protection
The transmitter congured data is saved by using a
write protection function. The write protection status
is set to “Yes” when 8 alphanumeric characters are
entered in the New password eld and transferred
to the transmitter.
When write protection is set toYes,” the transmitter
does not accept parameter changes. When the
same eight alphanumeric string entered in the New
password eld is also entered in the Enable wrt
10min eld and transferred to the transmitter, it
will be possible to change transmitter parameters
during a 10 minute period.
To change the transmitter from the write protection
”Yes” status back to write protection ”No” status,
use Enable wrt 10min to rst release the write
protection function and then enter eight spaces in
the New password eld.
Procedure to call up the display using by DD
and DTM (excluding EJX HART 5 DTM based
on FDT1.2)
DD and DTM
(excluding EJX_
HART 5[1.2])
[Root Menu] Detailed setup
Device information Field
device info Wrt protect menu
Write protect Display current protect mode
(Yes: protected, No: not
protected)
Enable wrt 10
min
Release the protect function for
10 min.
New password Set the new password or change
the password
Procedure to call up the display by EJX HART 5
DTM based on FDT1.2
EJX HART 5
DTM based on
FDT1.2
Write Protect
Write Protect Display current protect mode
(Yes: protected, No: not protected)
Enter new
password
Enter the password here to enable
the protect function.
Enter eight spaces to disable the
protect function.
Enable write Enter the password here to release
the protect function for 10 min.