User guide
IM 1C22H1-01E
8-6
8. MAINTENANCE
Connect BRAIN TERMINAL and check self-diagnostics.
Does the self-
diagnostic indicate problem
location?
Contact Yokogawa service personnel.
F0806.EPS
Is power supply
polarity correct?
Are high 
and low pressure side 
diaphragm seals correctly 
connected to the 
process?
Refer to error message summary in
Subsection 7.5.2 to take actions.
YES
NO
NO
YES
Check/correct polarity at each terminal 
from power supply to the terminal box.
Use the transmitter within the 
measurement range shown on the 
data plate.
Correct the connections.
NO
YES
YES
Adjust the zero point.
NO
NO
YES
Is the liquid level as specified?
Is zero point 
adjusted correctly?
Output travels beyond 0% or 100%.
Connect BRAIN TERMINAL and check self-diagnostics.
Contact Yokogawa service personnel.
F0807.EPS
Are power 
supply voltage and load 
resistance correct?
Is external noise 
contained in the outout?
Refer to error message summary in
Subsection 7.5.2 to take actions.
Bind capillaries together as far as 
possible or provide lagging.
Provide lagging and/or heat insulation, 
or allow adequate ventilation.
Refer to Section 8.2 when selecting
instruments for calibration.
Refer to Section 5.6 to obtain the rated
voltage and load resistance.
Avoid noise by providing complete 
grounding, or using shielded wires.
Adjust the output.
Does 
the ambient 
temperature significantly 
differ between the high and low 
pressure side
capillaries?
Is output adjusted correctly?
Large output error.
Does the self-
diagnostic indicate the problem
location?
Is transmitter
installed where there is 
marked variation in 
temperature?
Are excess 
capillaries secured?
YES
NO
YES
NO
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
Secure them so that they are not
moved by wind or vibration.
Were appropriate 
instruments used for 
calibration?
YES
NO