APPENDIX 1. LIST OF PARAMETERS FOR EACH BLOCK OF THE EJA
A1.3 Transducer Block
Relative
Index
Index ExplanationWrite ModeFactory DefaultParameter Name
0 2000 TAG: “TB”Block Header
Information on this block such as Block Tag, DD
Revision, Execution Time etc.
Block Tag
= O/S
1 2001 ST_REV
The revision level of the static data associated with the
function block. The revision value will be incremented
each time a static parameter value in the block is
changed.
2 2002 (blank)TAG_DESC
The user description of the intended application of the
block
AUTO
3 2003 1STRATEGY
The strategy field can be used to identify grouping of
blocks. This data is not checked or processed by the
block.
AUTO
4 2004 1ALERT_KEY
The identification number of the plant unit. This
information may be used in the host for sorting alarms,
etc.
AUTO
5 2005 AUTOMODE_BLK
The actual, target, permitted, and normal modes of the
block.
AUTO
6 2006 BLOCK_ERR
This parameter reflects the error status associated with
hardware or software components associated with a
block. It is a bit string, so that multiple errors may be
shown.
7 2007 UPDATE_EVT
This alert is generated by any change to the static data.
8 2008 BLOCK_ALM
The block alarm is used for all configuration, hardware,
connection failure or system problems in the block. The
cause of the alert is entered in the subcode field. The
first alert to become active will set the Active status in
the Status attribute.
9 2009 TRANSDUCER_
DIRECTORY
A directory that specifies the number and starting
indices of the transducers.
10 2010 100 (Standard Pre-
ssure with Calibration)
TRANSDUCER_
TYPE
Identifies transducer.
11 2011 XD_ERROR
The error code in transducer.
0=No failure
20=Electronics failure
22=I/O failure
21=Mechanical failure
12 2012 COLLECTION_
DIRECTORY
A directory that specifies the number, starting indices,
and DD Item Ids of the data collections in each
transducer within a transducer block.
13 2013 107: differential
pressure
108: gauge pressure
109:
absolute pressure
PRIMARY_
VALUE_TYPE
The type of measurement represented by primary
value.
Followings are available for EJA:
107=differential pressure
108=gauge pressure
109=absolute pressure
O/S
14 2014 PRIMARY_
VALUE
The measured value and status available to the function
block.
15 2015 Range of capsulePRIMARY_
VALUE_RANGE
The High and Low range limit values, engineering units
code and the number of digits to the right of the decimal
point to be used to display the primary value.
18 2018 Minimum span of
capsule
CAL_MIN_SPAN
The minimum calibration span value allowed.
16 2016 Max rangeCAL_POINT_HI
The highest calibrated value.O/S
17 2017 0CAL_POINT_LO
The lowest calibrated value.O/S
21 2021 Range of capsule
SENSOR_RANGE
TA0103-1.EPS
The High and Low range limit values, engineering units
code and the number of digits to the right of the decimal
point for the sensor.
19 2019 kPaCAL_UNIT
The engineering unit for the calibrated values.
20 2020 Silicon resonantSENSOR_TYPE
The type of sensor.