6-2
6. IN-PROCESS OPERATION
Update Alerts (Generated when a important
(restorable) parameter is updated)
By Resource Block Update Event
By Transducer Block Update Event
By AI1 Block Update Event
By AI2 Block Update Event
By PID Block Update Event
An alert has following structure:
Table 6.2 Alert Object
T0602.EPS
Parameter
Name
Explanation
1 Block Index
Index of block from which 
alert is generated
2 Alert Key
Alert Key copied from the 
block
3 Standard 
Type
Type of the alert
4Mfr Type
Alert Name identified by 
manufacturer specific DD
5
1
2
3
4
5Message 
Type
Reason of alert notification
1
2
3
6 Priority
Priority of the alarm
7 Time Stamp
Time when this alert is first 
detected
6
7
6
7
8 Subcode
Enumerated cause of this 
alert
9 Value
Value of referenced data
8
9
10 Relative 
Index
Relative index of referenced 
data
Static 
Revision
Value of static revision 
(ST_REV) of the block
10
8
11 Unit Index
Unit code of referenced data
11 9
4
5
Subindex
Analog
Alert
Discrete
Alert
Update
Alert
6.3 Simulation Function
The simulation function simulates the input of a
function block and lets it operate as if the data was
received from the transducer block. It is possible to
conduct testing for the downstream function blocks or
alarm processes.
A SIMULATE_ENABLE switch is mounted in the
EJA amplifier. This is to prevent the accidental
operation of this function. When this is switched on,
simulation is enabled. (See Figure 6.2.) To initiate the
same action from a remote terminal, if REMOTE
LOOP TEST SWITCH is written to the
SIM_ENABLE_MSG parameter (index 1044) of the
resource block, the resulting action is the same as is
taken when the above switch is on. Note that this
parameter value is lost when the power is turned OFF.
In simulation enabled status, an alarm is generated
from the resource block, and other device alarms will
be masked; for this reason the simulation must be
disabled immediately after using this function.
The SIMULATE parameter of AI block consists of the
elements listed in Table 6.3 below.
Table 6.3 SIMULATE Parameter
T0603.EPS
Sub-
index
Parameters Description
1Simulate Status
Sets the data status to be 
simulated.
2Simulate Value
Sets the value of the data 
to be simulated.
3Transducer Status
Displays the data status 
from the transducer block. 
It cannot be changed.
4Transducer Value
Displays the data value 
from the transducer block. 
It cannot be changed.
5Simulate En/Disable
Controls the simulation 
function of this block.
 1: Simulation disabled 
 (standard)
 2: Simulation started
When Simulate En/Disable in Table 6.3 above is set to
2, the applicable function block uses the simulation
value set in this parameter instead of the data from the
transducer block. This setting can be used for propaga-
tion of the status to the trailing blocks, generation of a
process alarm, and as an operation test for trailing
blocks.
F0602.EPS
Amplifier Assembly
1
2
O
N
"OFF" during operation
Not in use
SIM. ENABLE
Figure 6.2 SIMULATE_ENABLE Switch Position