4. GETTING STARTED
4.2 Host Setting
To activate Fieldbus, the following settings are
required for the host.
IMPORTANT
Do not turn off the power immediately after
setting. When the parameters are saved to the
EEPROM, the redundant processing is executed
for an improvement of reliability. If the power is
turned off within 60 seconds after setting is
made, the modified parameters are not saved
and the settings may return to the original
values.
Table 4.1 Operation Parameters
T0401.EPS
Symbol Parameter Description and Settings
Minimum value of 
communication data 
intervals. Unit of time is in 
octets (256 µs). Set the 
maximum specification for 
all devices. For EJA, set a 
value of 4 or greater.
Indicates the time 
necessary for immediate 
reply of thje device. Unit of 
time is in octets (256 µs). 
Set maximum specification 
for all devices. For EJA, 
set a value of 4 or greater. 
Slot-Time
V (ST)
First-Unpolled-Node
Minimum-Inter-PDU-
Delay
Maximum-Reply-
Delay
Unused address range. 
Indicate the address next 
to the address range used 
by the host. Set 0x15 or 
greater.
Number-of-
consecutive-
Unpolled-Node
The worst case time 
elapsed until a reply is 
recorded. The unit is Slot-
time; set the value so that 
V (MRD) !V (ST) is the 
maximum value of the 
specification for all 
devices. For EJA, the 
setting must be a value of 
12 or greater.
V (MRD)
V (MID)
V (FUN)
V (NUN)
Not used
0x00
0xF7
0xF8
0x0F
0x10
0x13
0x14
0xFB
0xFC
0xFF
V(FUN)
V(FUN)V(NUN)
LM device
Bridge device
Unused V(NUN)
Note 1: Bridge device: A linking device which brings data from one
 or more H1 networks.
Note 2: LM device: with bus control function (Link Master function)
Note 3: BASIC device: without bus control function
BASIC device
Default address
Portable device address
F0402.EPS
Figure 4.2 Available Address Range