Manual
Table Of Contents
- CONTENTS
- 1. INTRODUCTION
 - 2. HANDLING CAUTION
 - 3. ABOUT PROFIBUS PA
 - 4. GETTING STARTED
 - 5. CONFIGURATION
 - 6. CALIBRATION
 - 7. IN-PROCESS OPERATION
 - 8. DIAGNOSTIC INFORMATION
 - 9. GENERAL SPECIFICATIONS
 - APPENDIX 1. LIST OF PARAMETERS FOR EACH BLOCK OF THE EJA
 - APPENDIX 2. LIST OF DTM MENU
 - APPENDIX 3. LIST OF PDM (EDDL) MENU
 - REVISION RECORD
 
 

IM 01C22T03-00E
9-2
9. GENERAL SPECIFICATIONS
9.2 Optional Specifications
For items other than those described below, refer to
the appropriate user’s manual.
Item Description Code
Factory Mutual (FM)
CENELEC ATEX (KEMA) Flameproof Approval *
2
  Certificate: KEMA 02ATEX2148
  II 2G EEx d IIC T4, T5 and T6, Amb. Temp.: 40 to 80!C (40 to 176!F) for T5, 
  40 to 75!C (40 to 167!F) for T4 and T6
  Max. process Temp.: T4; 120!C (248!F), T5; 100!C (212!F), T6; 85!C (185!F)
  Enclosure: IP67
CENELEC ATEX Type n Approval *
2
    II 3G Ex nL IIC T4, Amb. Temp. –40 to 60°C (–40 to 140!F), Enclosure: IP67
      Ui=32V, Ci=3.52 nF, Li=0µH
CENELEC ATEX (KEMA) Intrinsically Safe Approval *
2
  Certificate: KEMA 02ATEX1344X
  [Entity model]
    II 1G EEx ia IIC T4, Amb. Temp.: 40 to 60!C (40 to 140!F) 
      Ui=24.0 V, Ii=250 mA, Pi=1.2 W, Ci=1.76 nF, Li=0 H
  [FISCO model]
    II 1G EEx ia IIC T4, Amb. Temp.: 40 to 60!C (40 to 140!F) 
      Ui=17.5 V, Ii=360 mA, Pi=2.52 W, Ci=1.76 nF, Li=0 H
    II 1G EEx ia IIB T4, Amb. Temp.: 40 to 60!C (40 to 140!F) 
      Ui=17.5 V, Ii=380 mA, Pi=5.32 W, Ci=1.76 nF, Li=0 H
  Enclosure: IP67
KF25
KN25
CF15
KS25
CENELEC ATEX
FF15
FS15
FM Explosionproof Approval *
1
  Explosionproof for Class I, Division 1, Groups B, C and D 
  Dust-ignitionproof for Class II/III, Division 1, Groups E, F and G
  Hazardous (classified) locations, indoors and outdoors (NEMA 4X)
  Temperature class: T6 Amb. Temp.:–40 to 60°C (–40 to 140°F) 
FM Intrinsically Safe Approval *
1
  [Entity Model]
Cl. I, II&III, Division 1, Groups A, B, C ,D, E, F&G, Temp. Cl. T4 and Cl. I, Zone 0, 
AEx ia IIC, Temp. Cl. T4
Groups A, B, C, D, E, F&G and Group IIC:
      Vmax.= 24 V, Imax.= 250 mA, Pi= 1.2 W, Ci= 3.52 nF, Li= 0 µH
  [FISCO Model]
Cl. I, II&III, Division 1, Groups A, B, C, D, E, F&G, Temp. Cl. T4 and Cl. I, Zone 0, 
AEx ia IIC, Temp. Cl. T4
Groups A, B, C, D, E ,F&G and Group IIC:
  Vmax.= 17.5 V, Imax.= 360 mA, Pi = 2.52 W, Ci = 3.52 nF, Li = 0µH
Groups C, D, E, F&G and Group IIB:
      Vmax.= 17.5V, Imax. = 380 mA, Pi = 5.32W, Ci = 3.52 nF, Li = 0µH
Nonincendive for Cl. I, Division 2, Groups A, B, C&D, Temp. Cl. T4
and Cl. I, Zone 2, Group IIC, Temp. Cl. T4
and Cl. II, Division 2, Groups F&G Temp. Cl. T4
and Cl. III, Division 2, Temp. Cl. T4
  Vmax.= 32 V, Ci = 3.52 nF, Li = 0µH
  Enclosure: “NEMA4X”, Amb. Temp.: –40 to 60°C (–40 to 140!F)
T0903.EPS
CSA Explosionproof Approval *
1
  Certificate: 1010820
  Explosionproof for Class I, Division 1, Groups B, C and D
  Dustignitionproof for Class II/III, Division 1, Groups E, F and G 
  Temp. Class: T4, T5, T6 Encl Type 4x Amb. Temp.: –40 to 80°C (–40 to 176°F)
 Max. Process Temp.: T4; 120°C (248°F), T5; 100°C (212°F), T6; 85°C (185°F)
Process Sealing Certification
 Dual seal certified by CSA to the requirement of ANSI/ISA 12.27.01
 No additional sealing required. Primary seal failure annunciation : at the zero adjust-
 ment screw 
Canadian Standards 
Association (CSA)
*1: Applicable for Electrical connection code 2 and 7.
*2: Applicable for Electrical connection code 2, 4, 7 and 9.