Manual
Table Of Contents
- CONTENTS
- 1. INTRODUCTION
 - 2. HANDLING CAUTION
 - 3. ABOUT PROFIBUS PA
 - 4. GETTING STARTED
 - 5. CONFIGURATION
 - 6. CALIBRATION
 - 7. IN-PROCESS OPERATION
 - 8. DIAGNOSTIC INFORMATION
 - 9. GENERAL SPECIFICATIONS
 - APPENDIX 1. LIST OF PARAMETERS FOR EACH BLOCK OF THE EJA
 - APPENDIX 2. LIST OF DTM MENU
 - APPENDIX 3. LIST OF PDM (EDDL) MENU
 - REVISION RECORD
 
 

IM 01C22T03-00E
8-1
8. DIAGNOSTIC INFORMATION
8. DIAGNOSTIC INFORMATION
Diagnostic information and failures of EJA are indicated by using parameter Diagnosis and Diagnosis Extension in
the Physical Block. Diagnosis and Diagnosis Extension are listed in Table 8.1 and 8.2 below.
Table 8.1 Contents of DIAGNOSIS
Octet
1
2
3
4
Bit
0
Mnemonic
DIA_HW_ELECTR
Description
Hardware failure: electronics
Remarks
--
Support
*1
1
2
3
DIA_TEMP_MOTOR Motor – temperature too high -- 0
5DIA_MEASUREMENT Failure in Measurement -- 0
6DIA_NOT_INIT
Device not initialized (No self calibration) 
-- 0
7DIA_INIT_ERR Self calibration failed -- 0
0DIA_ZERRO_ERR Zero point error (limit position) Zero adjustment error (AL.64) 1
2DIA_CONF_INVAL Configuration not valid -- 0
3DIA_WARMSTART
New-start-up (warm start up) carried out.
-- 0
4DIA_COLDSTART
Re-start-up (cold start up) carried out.
HW,SW,DL restart 1
5DIA_MAINTENANCE Maintenance required -- 0
6DIA_CHARACT Characterization invalid -- 0
0-7 Reserved Reserved for use within the PNO -- --
0-6 Reserved Reserved for use within the PNO -- --
7
EXTENSION_AVAILABLE
More diagnostic information is available
-- 1
7
IDENT_NUMBER_Viola-
tion
Set to 1 (one), if the Ident_Number 
of the running cyclic data transfer 
and the value of Physical Block 
IDENT_NUMBER_SELECTOR 
parameter are different.
-- 1
1DIA_SUPPLY
1 DIA_SUPPLY Power supply failed 
(electrical, pneumatic)
-- 0
DIA_TEMP_ELECTR Electronic temperature too high -- 0
1DIA_HW_MECH Hardware failure: mechanical
Capsule Module Failure1 (AL.01)
Capsule Module Failure2 (AL.01)
1
4DIA_MEM_CHKSUM Memory error
Capsule Module Failure3 (AL.01)
Amp Module Failure1 (AL.02)
Amp Module Failure2 (AL.03)
Amp Module Failure3 (AL.02)
1
T0801.EPS
*1 0: Not available for EJA