Manual
    <2. Handling Cautions>
7
IM 01C22A01-01E
•  Intrinsically Safe for Class I, Division 1, Groups A, 
B, C & D. Class II, Division 1, Groups E, F & G and 
Class III, Division 1 Hazardous Locations.
•  Nonincendive for Class I, Division 2, Groups A, B, C & 
D. Class II, Division 2, Groups E, F & G and Class III, 
Division 1 Hazardous Locations.
•  Outdoor hazardous locations, NEMA 4X.
• Temperature Class: T4
•  Ambient temperature: –40 to 60°C
Note 2.  Entity Parameters
• Intrinsically Safe Apparatus Parameters
  [Groups A, B, C, D, E, F and G]
  Vmax = 30 V, Ci = 22.5 nF, Imax = 165 mA, 
Li = 730 μH, Pmax = 0.9 W
*  Associated Apparatus Parameters 
(FM approved barriers)
 Voc ≤ 30 V, Ca > 22.5 nF, Isc ≤ 165 mA, La > 730 μH, 
Pmax ≤ 0.9W
•  Intrinsically Safe Apparatus Parameters
  [Groups C, D, E, F and G]
  Vmax = 30 V, Ci = 22.5 nF, Imax = 225 mA, 
Li = 730 μH, Pmax = 0.9 W
*  Associated Apparatus Parameters 
(FM approved barriers)
 Voc ≤ 30 V, Ca > 22.5 nF, Isc ≤ 225 mA, 
La > 730 μH, Pmax ≤ 0.9 W
•  Entity Installation Requirements
 Vmax ≥ Voc or Vt, Imax ≥ Isc or It, 
Pmax (IS Apparatus) ≥ Pmax (Barrier), 
Ca ≥ Ci + Ccable, La ≥ Li + Lcable
Note 3. Installation
•  Barrier must be installed in an enclosure that meets 
the requirements of ANSI/ISA S82.01.
•  Control equipment connected to barrier must not use 
or generate more than 250 V rms or V dc.
•  Installation should be in accordance with ANSI/ISA 
RP12.6 “Installation of Intrinsically Safe Systems for 
Hazardous (Classifi ed) Locations” and the National 
Electric Code (ANSI/NFPA 70).
•  The confi guration of associated apparatus must be 
FMRC Approved.
•  Dust-tight conduit seal must be used when installed in 
a Class II, III, Group E, F and G environments.
•  Associated apparatus manufacturer’s installation 
drawing must be followed when installing this 
apparatus.
•  The maximum power delivered from the barrier must 
not exceed 0.9 W.
•  Note a warning label worded “SUBSTITUTION OF 
COMPONENTS MAY IMPAIR INTRINSIC SAFETY,” 
and “INSTALL IN ACCORDANCE WITH DOC. No. 
IFM012-A12 P.1 and 2.”
Note 4. Maintenance and Repair
•  The instrument modifi cation or parts replacement by 
other than authorized representative of Yokogawa 
Electric Corporation is prohibited and will void Factory 
Mutual Intrinsically safe and Nonincendive Approval.
F0204.ai
Class I, II, III, Division 1, 
Groups A, B, C, D, E, F, G 
EJA Series Pressure 
Transmitters 
EJA Series Pressure 
Transmitters 
Safety Barrier 
Supply
Supply
Hazardous Location  Non-hazardous Location
Hazardous Location  Non-hazardous Location
General
Purpose
Equipment
+
–
+
–
+
–
+
–
+
–
+
–
[Intrinsically Safe] 
Class I, II, Division 2, 
Groups A, B, C, D, E, F, G 
Class III, Division 1. 
Not Use 
Safety Barrier 
[Nonincendive]
General
Purpose
Equipment
b. FM Explosionproof Type
  Caution for FM explosionproof type.
Note 1.  Model EJA Series differential, gauge, and 
absolute pressure transmitters with optional 
code /FF1 are applicable for use in hazardous 
locations.
•  Applicable Standard: FM3600, FM3615, FM3810, 
ANSI/NEMA250
•  Explosionproof for Class I, Division 1, Groups B, C 
and D.
•  Dust-ignitionproof for Class II/III, Division 1, Groups E, 
F and G.
•  Outdoor hazardous locations, NEMA 4X.
•  Temperature Class: T6
•  Ambient Temperature: –40 to 60°C
•  Supply Voltage: 42 V dc max.
•  Output signal: 4 to 20 mA
Note 2. Wiring
•  All wiring shall comply with National Electrical Code 
ANSI/NEPA70 and Local Electrical Codes.
•  When installed in Division 1, “FACTORY SEALED, 
CONDUIT SEAL NOT REQUIRED.”
Handling Cautions
2