Manual

<8. Parameter Summary>
31
IM 01C22A01-01E
No. Item Description
Rewrita-
bility
Remarks Default Value
Applicability
FPL
D30 TEMP UNIT Temperature setting units
deg C/deg F deg C

D31 STAT. P. UNIT Static pressure setting
units
Selected from mmH
2
O,
mmAq, mmWG, mmHg, Torr,
Pa, hPa, kPa, MPa, mbar,
bar, gf/cm
2
, kgf/cm
2
, inH
2
O,
inHg, ftH
2
O, psi, or atm
As speci ed when
ordered. If not
speci ed, MPa.
D40 REV OUTPUT Output reversal
NORMAL/REVERSE If not speci ed,
NORMAL.

D45 H/L SWAP Impulse piping accessing
direction
NORMAL/REVERSE*
4
NORMAL
——
D52 BURN OUT CPU error HIGH/LOW, –5 to 110%*
3
HIGH

D53 ERROR OUT Hardware error
HOLD/HIGH/LOW, –5 to
110%*
3
HIGH

D60 SELF CHECK Self-diagnostic messages Same as A60

E AUX SET 2 Auxiliary setting data 2 Menu name

E10 DFS MODE DFS mode
OFF/ON*
5
ON

E14 TEMP SELECT
Reference temperature sensor
AMP. TEMP/CAP. TEMP*
5
CAP. TEMP

E15 TEMP ZERO
Zero shift conpensation setup
±610.00*
5
0.00

E30 BI DIRE MODE Bidirectional mode
OFF/ON OFF
——
E50 AUTO RECOVER Auto-recover from sensor
error
OFF/ON ON

E60 SELF CHECK Self-diagnostic messages Same as A60

H AUTO SET Automatic setup Menu name

H10 AUTO LRV
Automatic measurement
range lower range value setup
–32000 to 32000 Displays the same
data as C21.

H11 AUTO HRV
Automatic measurement range
higher range value setup
–32000 to 32000 Displays the same
data as C22.

H60 SELF CHECK Self-diagnostic messages Same as A60

J ADJUST Adjustment data Menu name

J10 ZERO ADJ Automatic zero adjustment
–5 to 110.0%*
3

J11 ZERO DEV. Manual zero adjustment

J15 SPAN ADJ Manual span adjustment
–10.00 to 10.00% 0.00%

J20 EXT. ZERO ADJ External zero adjustment
screw permission
ENABLE/INHIBIT

J30 OUTPUT 4mA 4mA adjustment
–10.00 to 10.00% 0.00%

J31 OUTPUT 20mA 20mA adjustment
–10.00 to 10.00% 0.00%

J60 SELF CHECK Self-diagnostic messages Same as A60

K TEST Tests Menu name

K10 OUTPUT in % Test output % setting
–5 to 110.0%*
3
Displays
‘ACTIVE’ while executing

K60 SELF CHECK Self-diagnostic messages Same as A60

M MEMO Memo Menu name

M10 MEMO 1 Memo
8 uppercase alphanumerics

M20 MEMO 2 Memo
8 uppercase alphanumerics

M30 MEMO 3 Memo
8 uppercase alphanumerics

M40 MEMO 4 Memo
8 uppercase alphanumerics

M50 MEMO 5 Memo
8 uppercase alphanumerics

M60 SELF CHECK Self-diagnostic messages Same as A60

P RECORD History of the errors

P10 ERROR REC 1 Last error
Display the error

P11 ERROR REC 2 One time before
Display the error

P12 ERROR REC 3 Two time before
Display the error

P13 ERROR REC 4 Three time before
Display the error

P60 SELF CHECK Self-diagnostic messages Same as A60

*1: In case of Model EJA120A, static pressure cannot be measured. The display is always 0 MPa, but this is not a measured value.
*2: When Optional code /F1 is speci ed, substitute the value with 0.1.
*3: When Optional code /F1 is speci ed, substitute the value –5 with –2.5.
*4: Not applicable for Model EJA115.
*5: Applicable only for Model EJA118W, EJA118N, EJA118Y, EJA438W, and EJA438N.
*6: See MWP(max. working pressure) on the nameplate. B40 shows an approximate value of maximum pressure for the capsule.
*7: Unless otherwise speci ed by order. When Optional code /F1 is speci ed, substitute the value –5 with –2.5.
Parameter Summary
8