BRAIN Communication Parameter List
Instruments to which applicable:
F: Differential pressure transmitters:
EJA110A, EJA120A, EJA130A, EJA118W, EJA118N, EJA118Y, and EJA115
P: Pressure transmitters: EJA310A, EJA430A, EJA440A, EJA510A, EJA530A, EJA438W, and EJA438N
L: Liquid level transmitters: EJA210A and EJA220A
No. Item Description
Rewrita-
bility
Remarks Default Value
Applicability
FPL
01 MODEL Model+capsule type

02 TAG NO. Tag number 16 alphanumerics

03 SELF CHECK Self-diagnostic result GOOD/ERROR

A DISPLAY Measured data display Menu name

A10 OUTPUT (%) Output (in %) –5 to 110%*
3

A11 ENGR. OUTPUT Output (in engineering units) –19999 to 19999

A20 AMP TEMP Ampli er temperature Unit speci ed in D30

A21 CAPSULE TEMP Capsule temperature Unit speci ed in D30

A30 STATIC PRESS Static pressure Unit speci ed in D31*
1
A40 INPUT Input (indicated as the
value after zeroing)
–32000 to 32000

A60 SELF CHECK Self-diagnostic
messages
GOOD/ERROR, CAP MODULE FAULT, AMP
MODULE FAULT, OUT OF RANGE, OUT OF SP
RANGE*
1
, OVER TEMP (CAP),OVER TEMP
(AMP), OVER OUTPUT, OVER DISPLAY, ILLEGAL
LRV, ILLEGAL HRV, ILLEGAL SPAN, and ZERO
ADJ OVER

B SENSOR TYPE Sensor type Menu name

B10 MODEL Model+span 16 uppercase alphanumerics

B11 STYLE NO. Style number

B20 LRL Lower range-limit –32000 to 32000

B21 URL Upper range-limit –32000 to 32000

B30 MIN SPAN Minimum span –32000 to 32000

B40 MAX STAT.P. Maximum static pressure*
6
B60 SELF CHECK
Self-diagnostic
messages
Same as A60

C SETTING Setting data Menu name

C10 TAG. NO. Tag number
16 alphanumerics As speci ed when
ordered.

C20 PRESS UNIT Measurement range units
Selected from mmH
2
O,
mmAq,mmWG, mmHg,
Torr, Pa, hPa, kPa, MPa,
mbar, bar, gf/cm
2
, kgf/cm
2
,
inH
2
O, inHg, ftH
2
O, psi, or atm
As speci ed when
ordered.

C21 LOW RANGE Measurement range, lower
range value
–32000 to 32000(but within
measurement range)
As speci ed when
ordered.

C22 HIGH RANGE Measurement range,
higher range value
–32000 to 32000(but within
measurement range)
As speci ed when
ordered.

C30 AMP DAMPING Damping time constant
Selected from 0.2*
2
, 0.5, 1.0,
2.0, 4.0, 8.0, 16.0, 32.0, or
64.0 sec.
2.0 s

C40 OUTPUT MODE Output mode and integral
indicator mode
Selected from OUT:LIN; DSP:
LIN, OUT:LIN; DSP:SQR,
OUT:SQR; DSP:SQR
As speci ed when
ordered.
If not speci ed,
OUT: LIN; DSP: LIN.
——
C60 SELF CHECK Self-diagnostic messages Same as A60

D AUX SET 1 Auxiliary setting data 1 Menu name

D10 LOW CUT Low cut
0.0 to 20.0% 10.0%

D11 LOW CUT MODE Low cut mode
LINEAR/ZERO LINEAR

D15 OUT LIMIT(L) Lower output range-limit
–5.0 to 110.0% –5.0%*
7

D16 OUT LIMIT(H) Lower output range-limit
–5.0 to 110.0% 110.0%

D20 DISP SELECT Display selection
NORMAL %/USER SET, USER
& %/INP PRES, PRES & %
As speci ed when
ordered.

D21 DISP UNIT Engineering unit for display
8 uppercase alphanumerics

D22 DISP LRV Engineering range, lower
range value
–19999 to 19999 As speci ed when
ordered.

D23 DISP HRV Engineering range, higher
range value
–19999 to 19999 As speci ed when
ordered.
