  <7.  Errors and Countermeasures>
28
IM 01C22A01-01E
7.  Errors and Countermeasures
NOTE
For FOUNDATION Fieldbus and PROFIBUS PA communication types, please refer to manuals in the attached CD-ROM.
The table below shows a summary of error messages for BRAIN and HART protocols.
Table 7.1  Error Message Summary
Integral 
Indicator 
Display
Description Cause Output Operation during Error Countermeasure
None GOOD
--- ERROR
Er. 01 CAP MODULE FAULT Capsule problem.*
1
Outputs the signal according to 
status of a burnout direction pin 
or switch (the signal can be set as 
“hold” for BRAIN protocol).
Replace the capsule when 
error keeps appearing even 
after restart.*
2
Er. 02 AMP MODULE FAULT Amplifi er problem. Outputs the signal (Hold, Outputs 
the signal according to status of 
a burnout direction pin or switch 
(the signal can be set as “hold” for 
BRAIN protocol).
Replace amplifi er.
Er. 03 OUT OF RANGE Input is outside 
measurement range limit 
of capsule.
Outputs high range limit value or 
low range limit value.
Check input.
Er. 04 OUT OF SP RANGE Static pressure exceeds 
specifi ed range.*
3
Displays present output. Check line pressure (static 
pressure).
Er. 05 OVER TEMP (CAP) Capsule temperature 
is outside range (-50 to 
130°C).
Displays present output. Use heat insulation or make 
lagging to keep temperature 
within range.
Er. 06 OVER TEMP (AMP) Amplifi er temperature 
is outside range (-50 to 
95°C).
Displays present output. Use heat insulation or make 
lagging to keep temperature 
within range.
Er. 07 OVER OUTPUT Output is outside high or 
low range limit value.
Outputs high or low range limit 
value.
Check input and range 
setting, and change them as 
needed.
Er. 08 OVER DISPLAY Displayed value is 
outside high or low range 
limit value.
Displays high or low range limit 
value.
Check input and display 
conditions and modify them 
as needed.
Er. 09 ILLEGAL LRV LRV is outside setting 
range.
Holds output immediately before 
error occurrence.
Check LRV and modify as 
needed.
Er. 10 ILLEGAL URV URV is outside setting 
range.
Holds output immediately before 
error occurrence.
Check URV and modify as 
needed.
Er. 11 ILLEGAL SPAN SPAN is outside setting 
range.
Holds output immediately before 
error occurrence.
Check SPAN and change as 
needed.
Er. 12 ZERO ADJ OVER Zero adjustment is too 
large.
Displays present output. Readjust zero point.
*1:  This error code appears at a capsule problem or when an illegal overpressure is applied to the pressure sensor. 
*2:  If the normal pressure is regained, the Er.01 will disappear according to the setting of the parameter of E50:AUTO RECOVER.
When the E50:AUTO RECOVER is set to ON, the Er.01 will disappear automatically. The default setting for this parameter is 
ON. When the E50:AUTO RECOVER is set to OFF, restart the transmitter to cancel Er.01. If no error code appears then, perform 
necessary adjustments such as zero-adjustment to continue the operation. If the error code still appears, replace the capsule 
assembly.
*3:  For Model EJA120A, static pressure cannot be measured. The display is always 0 MPa, but this is not a measured value.