Manual
  <5. Wiring>
23
IM 01C22A01-01E
5. Wiring
NOTE
For FOUNDATION Fieldbus and PROFIBUS PA 
communication types, please refer to manuals in the 
attached CD-ROM.
5.1 Wiring Precautions
IMPORTANT
•  Lay wiring as far as possible from electrical noise 
sources such as large capacity transformers, 
motors, and power supplies.
•  Remove electrical connection dust cap before 
wiring.
•  All threaded parts must be treated with 
waterproofi ng sealant. (A non-hardening silicone 
group sealant is recommended.)
•  To prevent noise pickup, do not pass signal and 
power cables through the same ducts.
•  Explosion-protected instruments must be wired 
in accordance with specifi c requirements (and, 
in certain countries, legal regulations) in order 
to preserve the effectiveness of their explosion-
protected features.
•  The terminal box cover is locked by an Allen head 
bolt (a shrouding bolt) on CENELEC and IECEx 
fl ameproof type transmitters. When the shrouding 
bolt is driven clockwise by an Allen wrench, it is 
going in and cover lock is released, and then the 
cover can be opened by hand.
When a cover is closed it should be locked by a 
shrouding bolt without fail. Tighten the shrouding 
bolt to a torque of 0.7 N·m.
Shrouding Bolt
Shrouding Bolt
F0501.ai
5.2  Connections of External 
Wiring to Terminal Box
5.2.1  Power Supply Wiring Connection
Connect the power supply wiring to the SUPPLY + and 
– terminals.
Power supply
–
+
Transmitter terminal box
F0502.ai
Figure 5.1  Power Supply Wiring Connection
5.2.2  Handheld Terminal Connection
Connect the handheld terminal to the SUPPLY + and 
– terminals (Use hooks). Communication line requires a 
reception resistor of 250 to 600Ω in series.
Transmitter terminal box
BT200 etc.
F0503.ai
Power supply
–
+
Ignore the polarity
since it is AC-coupled 
to the terminal box.
250 to 600 Ω
Figure 5.2  Handheld Terminal Connection
5.3 Wiring
CAUTION
For the intrinsically safe equipment and fl ameproof 
equipment, wiring materials and wiring work for these 
equipment including peripherals are strictly restricted. 
Users absolutely must read “Installation and Operating 
Precautions for TIIS Intrinsically Safe Equipment” 
and “Installation and Operating Precautions for TIIS 
Flameproof Equipment” at the end of this manual prior 
to the work.
Wiring
5