Manual
    <4. Installing Impulse Piping>
20
IM 01C22A01-01E
4)  Now tighten the nuts and bolts securely in the 
following sequence:
Process connector bolts → transmitter-end ball head 
lock nuts → 3-valve manifold ball head lock nuts → 
3-valve manifold mounting bracket U-bolt nuts 
 Direct-Mounting Type 3-Valve Manifold
1)  Mount the 3-valve manifold on the transmitter. (When 
mounting, use the two gaskets and the four bolts 
provided with the 3-valve manifold. Tighten the bolts 
evenly.)
2)  Mount the process connectors and gaskets on the top 
of the 3-valve manifold (the side on which the impulse 
piping will be connected.)
Bolts
Process
connector
Gasket
Gasket
Process
connector
Bolts
Stop valve
Stop valve
3-valve manifold
3-valve
manifold
Equalizing valve
Equalizing
valve
Stop valve
Impulse
piping
Impulse
piping
Stop valve
F0404.ai
Figure 4.4  3-Valve Manifold 
(Direct-Mounting Type)
4.1.2  Routing the Impulse Piping
(1)  Process Pressure Tap Angles
If condensate, gas, sediment or other extraneous 
material in the process piping gets into the impulse 
piping, pressure measurement errors may result. To 
prevent such problems, the process pressure taps must 
be angled as shown in Figure 4.5 according to the kind of 
fl uid being measured.
NOTE
•  If the process fl uid is a gas, the taps must be 
vertical or within 45° either side of vertical.
•  If the process fl uid is a liquid, the taps must be 
horizontal or below horizontal, but not more than 
45° below horizontal.
•  If the process fl uid is steam or other condensing 
vapor, the taps must be horizontal or above 
horizontal, but not more than 45° above horizontal.
[Gas]
Pressure
taps
Process
piping
[Steam][Liquid]
45°
45°
45° 45°
45°
45°
F0405.ai
Figure 4.5  Process Pressure Tap Angle 
(For Horizontal Piping)
(2)  Position of Process Pressure Taps and 
Transmitter
If condensate (or gas) accumulates in the impulse piping, 
it should be removed periodically by opening the drain 
(or vent) plugs. However, this will generate a transient 
disturbance in the pressure measurement, and therefore 
it is necessary to position the taps and route the impulse 
piping so that any extraneous liquid or gas generated in 
the leadlines returns naturally to the process piping.
•  If the process fl uid is a gas, then as a rule the 
transmitter must be located higher than the process 
pressure taps.
•  If the process fl uid is a liquid or steam, then as a 
rule the transmitter must be located lower than the 
process pressure taps.
(3)  Impulse Piping Slope
The impulse piping must be routed with only an upward or 
downward slope. Even for horizontal routing, the impulse 
piping should have a slope of at least 1/10 to prevent 
condensate (or gases) from accumulating in the pipes.
(4)  Temperature Difference Between Impulse 
Piping
If there is a temperature difference between the high and 
low impulse piping, the density difference of the fl uids 
in the two lines will cause an error in the measurement 
pressure. When measuring fl ow, impulse piping must be 
routed together so that there is no temperature difference 
between them.










