    <3. Installation>
16
IM 01C22A01-01E
3.2.1  EJA210A and EJA220A
The transmitter is mounted on a process using its 
high pressure side fl ange as shown in Figure 3.5. The 
customer should prepare the mating fl ange, gasket, stud 
bolts and nuts.
Gasket
Stud bolt
Nut
F0305.ai
Figure 3.5  EJA210A and EJA220A Mounting
3.2.2 EJA118 and EJA438
Mount the diaphragm seals using the fl anges as shown 
in Figure 3.6. The customer should prepare the mating 
fl ange, gasket, bolts and nuts.
Nut
Flange
Diaphragm
ød
Gasket
F0306.ai
Bolt
The product is 
shipped with these 
parts assembled.
Correctly install the diaphragm 
seals on the high and low pressure 
sides of the process, checking the 
label on each seal.
Figure 3.6  Mounting the Diaphragm Seals
3.3 Diaphragm Seals Installation 
Consideration
IMPORTANT
•  When measuring the liquid level of the tank, the 
minimum liquid level (zero point) must be set to a 
level at least 50 mm above the center of the high 
pressure side diaphragm seal (see Figure 3.2.3).
•  Correctly install the diaphragm seals on the high 
and low pressure sides of the process, checking 
the label on each seal.
•  To avoid measuring error duets temperature 
difference between the two diaphragm seals, 
capillary tube must be bound together. The 
capillary tube must be securely fi xed to the tank 
wall to prevent movement by wind or vibration. 
If the capillary tube is too long, loosely coil the 
excess and secure using suitable clamps.
F0307.ai
Low
pressure
side
High
pressure
side
50mm minimum
Minimum
liquid level
Install the sealed diaphragm 
so that the shank positions 
downward.
IMPORTANT
The transmitter should be installed as low 
as possible below the position where the 
high pressure side diaphragm seal is 
installed.
Figure 3.7  Installing the Diaphragm Seals to a 
Tank