    <2. Handling Cautions>
12
IM 01C22A01-01E
Note 5.  Maintenance and Repair
•  The instrument modifi cation or parts replacement by 
other than authorized representative of Yokogawa 
Electric Corporation is prohibited and will void KEMA 
Flameproof Certifi cation.
c.  CENELEC ATEX (KEMA) Intrinsically Safe 
Type/CENELEC ATEX (KEMA) Flameproof 
Type/CENELEC ATEX Type n
Model EJA-A Series pressure transmitters with 
optional code /KU2 can be selected the type of 
protection CENELEC ATEX (KEMA) Intrinsically Safe, 
Flameproof or CENELEC ATEX Type n for use in 
hazardous locations.
Note 1.  For the installation of this transmitter, once a 
particular type of protection is selected, any 
other type of protection cannot be used.
The installation must be in accordance with the 
description about the type of protection in this 
user’s manual.
Note 2.  In order to avoid confusion, unnecessary 
marking is crossed out on the label other 
than the selected type of protection when the 
transmitter is installed.
●  CENELEC ATEX Type of Protection “n”
WARNING
When using a power supply not having a nonincendive 
circuit, please pay attention not to ignite in the 
surrounding fl ammable atmosphere.
In such a case, we recommend using wiring metal 
conduit in order to prevent the ignition.
•  Applicable Standard: EN60079-15
•  Referential Standard: IEC60079-0, 
IEC60079-11
•  Type of Protection and Marking Code: Ex nL IIC T4
• Temperature Class: T4
• Enclosure: IP67
•  Process Temperature: 120°C max.
•  Ambient Temperature: –40 to 60°C
Note 1.  Electrical Data
  Ui = 30 V
  Effective internal capacitance; Ci = 22.5 nF
  Effective internal inductance; Li = 730 μH
Note 2. Installation
•  All wiring shall comply with local installation 
requirements. (refer to the installation diagram)
Note 3.  Maintenance and Repair
•  The instrument modifi cation or parts replacement by 
other than authorized representative of Yokogawa 
Electric Corporation is prohibited and will void Type of 
Protection “n”.
Power Supply 
(Zone 2 only) 
Transmitter 
Supply
Non-hazardous Location
[Installation Diagram]
Hazardous Location 
+
–
+
–
F0210.ai
Ratings of the Power Supply as follows; Maximum Voltage: 30 V
●  CENELEC ATEX Type of Protection “Dust”
•  Applicable Standard: EN50281-1-1:1997
•  Type of Protection and Marking Code: II 1D
• Maximum Surface Temperature:
T65°C (Tamb.: 40°C), T85°C (Tamb.: 60°C), and 
T105°C (Tamb.: 80°C)
Note 1.  Installation instructions
  The cable entry devices and blanking elements 
shall be of a certifi cated type providing a level of 
ingress protection of at least IP6x, suitable for 
the conditions of use and correctly installed.
(2) Electrical Connection
The type of electrical connection is stamped near the 
electrical connection port according to the following 
marking.
F0211.ai
Location of the marking
Screw Size Marking
ISO M20 × 1.5 female M
AANSI 1/2 NPT female
(3) Installation
WARNING
•  All wiring shall comply with local installation 
requirement and local electrical code.
•  There is no need of the conduit seal for both of 
Division 1 and Division 2 hazardous locations 
because this product is sealed at factory.
•  In case of ANSI 1/2 NPT plug, ANSI hexagonal 
wrench should be applied to screw in.