    <2. Handling Cautions>
8
IM 01C22A01-01E
Note 3.   Operation
•  Keep the “CAUTION” nameplate attached to the 
transmitter.
  CAUTION: OPEN CIRCUIT BEFORE 
REMOVING COVER. FACTORY SEALED, 
CONDUIT SEAL NOT REQUIRED. INSTALL 
IN ACCORDANCE WITH THE INSTRUCTION 
MANUAL IM 1C22.
•  Take care not to generate mechanical sparking when 
accessing to the instrument and peripheral devices in 
a hazardous location.
Note 4. Maintenance and Repair
•  The instrument modifi cation or parts replacement by 
other than authorized representative of Yokogawa 
Electric Corporation is prohibited and will void Factory 
Mutual Explosionproof Approval.
c.  FM Intrinsically Safe Type/FM 
Explosionproof Type
Model EJA Series pressure transmitters with optional 
code /FU1 can be selected the type of protection (FM 
Intrinsically Safe or FM Explosionproof) for use in 
hazardous locations.
Note 1. For the installation of this transmitter, once a 
particular type of protection is selected, any 
other type of protection cannot be used. The 
installation must be in accordance with the 
description about the type of protection in this 
instruction manual.
Note 2. In order to avoid confusion, unnecessary 
marking is crossed out on the label other 
than the selected type of protection when the 
transmitter is installed.
2.4.2 CSA Certifi cation
a.   CSA Intrinsically Safe Type
Caution for CSA Intrinsically safe type. (Following 
contents refer to “DOC No. ICS003-A12 P.1-1 and 
P.1-2.”)
Note 1. Model EJA Series differential, gauge, and 
absolute pressure transmitters with optional 
code /CS1 are applicable for use in hazardous 
locations
Certifi cate: 1053843
•  Applicable Standard: C22.2 No.0, No.0.4, No.25, 
No.30, No.94, No.142, No.157, No.213
•  Intrinsically Safe for Class I, Division 1, Groups A, 
B, C & D. Class II, Division 1, Groups E, F & G and 
Class III, Division 1 Hazardous Locations.
•  Nonincendive for Class I, Division 2, Groups A, B, C 
& D, Class II, Division 2, Groups F & G, and Class III, 
Hazardous Locations. (not use Safety Barrier)
•  Encl. “Type 4X”
•  Temperature Class: T4
•  Ambient temperature: –40 to 60°C
•  Process Temperature: 120°C max.
Note 2  Entity Parameters
•  Intrinsically safe ratings are as follows:
  Maximum Input Voltage (Vmax) = 30 V
  Maximum Input Current (Imax) = 165 mA
  Maximum Input Power (Pmax) = 0.9 W
  Maximum Internal Capacitance (Ci) = 22.5 nF
  Maximum Internal Inductance (Li) = 730 μH
*  Associated apparatus (CSA certifi ed barriers)
  Maximum output voltage (Voc) ≤ 30 V
  Maximum output current (Isc) ≤ 165 mA
  Maximum output power (Pmax) ≤ 0.9 W
Note 3. Installation
•  All wiring shall comply with Canadian Electrical Code 
Part I and Local Electrical Codes.
•  The instrument modifi cation or parts replacement by 
other than authorized representative of Yokogawa 
Electric Corporation and Yokogawa Corporation 
of America is prohibited and will void Canadian 
Standards Intrinsically safe and nonincendive 
Certifi cation.
F0205.ai
Class I, II, III, Division 1,
Groups A, B, C, D, E, F, G
EJA Series Pressure 
Transmitters
EJA Series Pressure 
Transmitters
Safety Barrier
Supply
Supply
Hazardous Location Non-hazardous Location
Hazardous Location Non-hazardous Location
General
Purpose
Equipment
+
–
+
–
+
–
+
–
+
–
+
–
[Intrinsically Safe]
Class I, II, Division 2,
Groups A, B, C, D, E, F, G
Class III, Division 1.
Not Use
Safety Barrier
[Nonincendive]
General
Purpose
Equipment
b.  CSA Explosionproof Type
Caution for CSA explosionproof type.
Note 1. Model EJA Series differential, gauge, and 
absolute pressure transmitters with optional 
code /CF1 are applicable for use in hazardous 
locations:
Certifi cate: 1089598
•  Applicable Standard: C22.2 No.0, No.0.4, No.25, 
No.30, No.94, No.142
•  Explosionproof for Class I, Division 1, Groups B, C 
and D.
•  Dust-ignitionproof for Class II/III, Division 1, Groups E, 
F and G.
•  Encl “Type 4X”