Operation Manual
    <9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>
9-7
IM 01F06A00-01EN
e.  Burst Mode
When the Burst mode is set to Wired HART 
Enabled, the device starts to send the data.
•  Procedure to call up the display
[Root Menu]  Detailed setup  Confi gure 
outputs  HART output  Burst condition  Burst 
Message1, 2 or 3  Burst mode  Wired HART 
Enabled
9.10.3 Event Notifi cation
When a setting change and a change of the Self-
diagnostics occur, device detect it as an event and 
can transmit an alarm signal continuously.
Alarm contained in the following item can be set to 
Event, and can be detected.
• Device Status
•  Status group 1 to 3
•  Ext dev status
•  Device diagnostic status 0
Up to four events that occurred can be stored. 
When using this function, set to Burst mode as 
“Wired HART Enabled”.
(1) Set Event Notifi cation
•  Procedure to call up the display
DD (HART 7)
DTM (HART 7)
[Root Menu]  Detailed setup  
Confi gure outputs  HART output 
Event Notifi cation
 Event 
Notifi cation 
Control
Stop the event monitor: OFF
Shift to the monitor state: 
Enable event notifi cation on token-
passing data 
link layer
 Event Mask Set the status to detect
 Event 
Notifi cation 
Retry Time
Set the retry time when the event occur.
 Max Update 
Time
Set the retry time when the event does 
not occur.
 Event Debounce 
Interval
The setting of the minimum event 
duration
a) Event Mask
Set the status to detect in the Event Mask 
parameter.
Device Status Mask
Status group 1 to 3
Ext dev status Mask
Device Diagnostic Status 0 Mask
b) Event Notifi cation Retry Time/ Max 
Update Time/ Event Debounce Interval
Set to Event Notifi cation Retry Time, Max 
Update Time and Event Debounce Interval.
For Event Noteifi cation Retry Time, set the 
value thet is smaller than Max Update Time.
Event Notifi cation Retry 
Time/Max Update Time
Event Debounce Interval
—Off
0.5 s 0.5 s
1 s 1 s
2 s 2 s
4 s 4 s
8 s 8 s
16 s 16 s
32 s 32 s
1 min 1 min
5 min 5 min
10 min 10 min
15 min 15 min
30 min 30 min
45 min 45 min
60 min 60 min
c) Event Notifi cation Control
Select “Enable event notifi cation on token-passing 
data link layer” in the Event Notifi cation Control 
parameter to shift to the monitor state:
(2) Acknowledge Event Notifi cation (DTM)
The transmission of the event message stops 
when event is approved.
•  Procedure to call up the display
DTM (HART 7) [Root Menu]  Detailed setup  
Confi gure outputs  HART output 
Event Notifi cation  Knowledge 
 Acknowledge 
Event 
Notifi cation
Acquisition of the event number and 
approval.
a)  Get Event Number
Confi rm the latest event number.
Execute Acknowledge Event Notifi cation 
method.
1) Set “0” to enter Event Number.
2) OK.
3) Set “Trans 0: Read Event Notifi cation” to 
Select Transaction.
4) OK.
5) Confi rm Event Number.