Operation Manual

<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>
9-4
IM 01F06A00-01EN
Table 9.1 Burst parameters
Command parameter Burst Command
Burst Msg Trigger
Mode
Burst Trigger Source Burst Trigger Units
PV
( ow rate)
Cmd1:PV Continuous
Window PV Depends on the
assigned variable to
PV
Rising
Falling
On-change
% range/current
(Percent of range, Loop current)
Cmd2: % range/
current
Continuous
Window % range %
Rising
Falling
On-change
Process vars/current
(Loop current, PV, SV, TV, QV)
Cmd3:Dyn vars/
current
Continuous
Window PV Depends on the
assigned variable to
PV
Rising
Falling
On-change
Process vars/%range/current with status
*1
(Select from ow rate, total ow,
temperature, density, percent of range,
loop current, PV, SV, TV, and QV)
*2
Cmd9:Device vars w/
Status
Continuous
Window Top of Burst Device
Variables
Depends on maapping
Rising
Falling
On-change
Process vars/%range/current
(Select from ow rate, total ow,
Temperature, Density, percent of range,
loop current, PV, SV, TV, and QV)
*2
Cmd33:Device
Variables
Continuous Top of Burst Device
Variables
Depends on the
assigned variable to
Burst Device Variable
Window
Rising
Falling
On-change
Self diagnosis information
Cmd48:Read
Additional Device Status
Continuous
On-change All status
*1: Output the data with time and status.
*2: Select at Burst Device Variables
Update time period of each measurement value is
as follows;
Flow rate: Flow rate Update time period
Total: Total Update time period
Temperature: Temperature Update time period
Density: Density Update time period
9.10.2 Burst Mode
When the Burst mode is enabled, the device
continuously sends up to three data listed in Table
9.1.
When the Burst mode is set to “Wired HART
Enabled”, the device continuously sends alarm
signal also.
Refer to Subsection 9.10.3 “Event Noti cation” for
detail.
When changing the setting of Burst mode, set “Off”
to the Burst mode. Default setting is “Off”.
(1) Burst Message
The parameters for Burst Message are as
follows.
Transmit data: command parameters of Burst
Command
• Device variables:
• Update period
Transmit condition: choice in Burst Msg Trigger
Mode
Refer to Table 9.1 for the combination between
command parameter and transmit condition.
[Root Menu] Detailed setup Con gure
outputs HART output Burst Condition
Burst Message1, 2, 3 Burst command
NOTE
• In case of Burst Mode setting change, con rm
Burst Mode parameter is OFF.
• Prioritize to use the 'Burst Message 1'.