    <7. OPERATION FOR THE BRAIN TERMINAL (BT200)>
7-4
IM 01F06A00-01EN
(2) Setting Output
Example: Change the pulse output to alarm output
F0705.ai
Enter menu item, and press 
“ ” key.
Move the inverse video bar 
to “B : EASY SETUP”.
Item B menu is displayed.
Move the inverse video bar 
to “B20 : CONTACT OUT”.
Pressing “ENTER”, cause 
the data setup screen to be 
displayed.
If the security screen 
appears, 
enter the security code.
Move the inverse video bar 
to “ALARM”.
2 Times
4 Times
Pressing the enter key, 
inverse video bar is flashed.
The data setting can be 
completed.
If data setting is missing, 
press “F3” key and rewrite 
the data.
Setting is completed.
The screen returns to the 
preceding screen when the 
“F4” (ESC) key is pressed.
MENU
A:DISPLAY
B:EASY SETUP
C:BASIC SETUP
D:AUX. SETUP
E:METER SETUP
H:ADJUST
HOME SET ADJ ESC
PARAM
B10:FLOW SPAN
 100 m3/h
B15:DAMPING
 4 sec
B20:CONTACT OUT
 SCALED PULSE
DATA DIAG PRNT ESC
PARAM
B10:FLOW SPAN
 100 m3/h
B15:DAMPING
 4 sec
B20:CONTACT OUT
 SCALED PULSE
DATA DIAG PRNT ESC
PARAM
B10:FLOW SPAN
 100 m3/h
B15:DAMPING
 4 sec
B20:CONTACT OUT
 ALARM
DATA DIAG PRNT ESC
SET
B20:CONTACT OUT
 SCALED PULSE
< OFF >
< SCALED PULSE >
<UNSCALED PULSE>
 ESC
SET
B20:CONTACT OUT
 SCALED PULSE
<UNSCALED PULSE>
< FREQUENCY >
< ALARM >
 ESC
SET
B20:CONTACT OUT
 SCALED PULSE
 ALARM 
Print off
F2:printer on
FEED POFF NO
SET
B20:CONTACT OUT
 ALARM 
FEED NO OK
IMPORTANT
After setting a parameter, keep the power on for 
at least 30 seconds.
If the power of fl owmeter is turned off, a 
parameter setting is released.