Operation Manual
    <6. PARAMETERS>
6-18
IM 01F06A00-01EN
• Defi nition of error varies with the type of 
fl owmeter. Be careful of the difference in signs 
in the error and corrected value.
Q
f
 =
f(Hz)
 100
K-factor
  holds and the error is included in the K-factor.
 Therefore, for the region where the K-factor 
shift on the positive side, the corrected value is 
negative.
 The corrected value when the calibration fl uid 
of the fl owmeter and the fl uid to be measured 
are different must be set as a corrected value 
obtained by making both abscissas agree with 
respect to the Reynolds number.
(8)  Item J (TEST)
These items are for test of output.
A value in “( )” is the data corresponding to indicator.
The test output by setting in J10, J20 or J30 is 
automatically released when shifts from these 
parameter items or as following time goes without 
access to these parameter items.
“K50: SOFTWARE REV” = “6.20” or less: 10 
minutes
“K50: SOFTWARE REV” = “7.00” or greater: a 
value set in J40: RELEASE TIME
[J10:OUT ANALOG] 4 to 20mA Current 
output
It tests 4 to 20mA Current output. Electric current of 
the set value (%) which designates 4 to 20mA as 0 
to 100%.
When this test is executed, transistor contact output 
(Pulse, Alarm, Status) is fi xed at ON or OFF (not 
determined).
[J20:OUT PULSE] Pulse output
It tests Pulse output. 
The number of pulses which is set (unit: PPS) is 
output.
Exiting this parameter item or stopping access after 
ten minutes which is set in J40, this function will be 
reset automatically.
When this test is executed, current output is fi xed at 
0% (4mA).
[J30:OUT STATUS] Status output test
Status output test can be executed (OFF(0) or 
ON(1)).
When this test is executed, current output is fi xed at 
0% (4mA).
Exiting this parameter item or stopping access after 
ten minutes, this function will be reset automatically.
[J40:RELEASE TIME] Release time
Automatic reset time of J10, J20 and J30 can be 
change.
Select from 10min (0), 30min (1), 60min (2), 3h (3), 
6h (4), or 12h (5). 
(9)  Item K (Maintenance)
These items are for maintenance.
A value in “( )” is the data corresponding to indicator.
[K10:TLA] TLA Adjustment
Trigger level (TLA) is adjusted upon shipment. 
Therefore, TLA adjustment is nonnecessity. But set 
TLA adjustment below as
•  The measurement of Low fl ow rate area is 
required.
•  Mechanical vibration and impact are applied 
to digitalYEWFLO and Zero point and low fl ow 
rate area is output.
Note: Refer to Section 10.2 “Adjustment for 
Manual Mode”.
[K20:SIGNAL LEVEL] Signal Level
Set the signal level.
[K25:N. B. MODE] Noise Balance Mode
Set the Noise Balance Mode from “AUTO(0)”, 
“MANUAL(1)”, or “TUNING AT ZERO(2)”
[K26:N. B.RATIO] The ratio of Noise 
Balance
When “NOISE BALANCE MODE (N. B. MODE)” is 
“AUTO”, noise balance value is the indication only.
When N.B. mode is “MANUAL”, the noise balance 
can be adjusted entering the setting values.
Note: Refer to Section 10.2 “Adjustment for Manual 
Mode”. 
[K28:SET VORTEX F] Output test by setting 
simulated frequency
Amplifi er check is executed by simulated frequency 
input.
Output to be able to check are, analog output, pulse 
output/contact output.
Test status also can be seen on display board.