<6. PARAMETERS>
6-14
IM 01F06A00-01EN
[C40:TIME UNIT] TIME UNIT
Select time unit from “/s(0), /m(1), /h(2), /d(3)”
[C45:FLOW SPAN] Flowrate span
Set the required span with a numerical value.
[C50:DAMPING] Damping time constant
Set damping time constant values from 0 to 99s.
(4) Item D (AUX. SETUP)
These items are for Auxiliary setup.
A value in “( )” is the data corresponding to indicator.
[D10:LOW CUT] Low-cut owrate
NOTE
For D10 setting, be sure to set “NOMINAL SIZE”
in E10 rstly.
Set to noise elimination or zero ow in the low
owrate (or low frequency) range. The settable
range for low cut owrate is more than half-
minimum owrate.
NOTE
In case that Reynolds adjustment (H25), Gas
expansion correction (H30) or select a break
point correction (H40) is necessary to set,
D10: LOW CUT must be set after the items
for compensations (H25, H30, H40) are set to
“ACTIVE”.
[D20:TEMP UNIT] Fluid temperature unit at
operating conditions
Select temperature unit at operating condition from
deg C (0), deg F (1).
[D21:TEMP f] Fluid temperature at
operating conditions
Set uid temperature at operating condition.
[D25:DENSITY UNIT] Density Unit of Flow
measurement
Select the unit of density from kg/m
3
(0), lb/cf(1), lb/
USgal(2), lb/UKgal(3).
[D26:DENSITY f] Density at normal
operation conditions
Set the density value of the uid at operating
condition for mass ow unit
[D30:OUT LIMIT] Limit value of output and
indication
Set limit value of output from 100.0% to 110.0%
[D35:BURN OUT] Indication of the output
direction at burn out
This is indication of the output direction at burn
out. Refer to Subsection 10.1.6 “Setting of Burnout
Switch” when the output direction can be changed.
[D40:SPECIAL UNIT] Change to special
owrate unit
No(0) : Off the function
Yes(1) : Convert the ow unit for USER’S UNIT
The factor to convert the ow unit comes
from D43. The time unit comes from C40 or
F35.
Special(2) : Convert the ow unit and time unit for
the USER’S UNIT.
The factor to convert the ow unit and
time unit comes from D43.
[D41:BASE UNIT] Indication of the base
owrate unit
Indication of the basic owrate unit when item D40
is “Yes(1)” or “Special(2)”.
[D42:USER'S UNIT] Free unit for users
Set in up to 8 alphanumeric characters when item
D40 is “Yes(1)” or “Special(2)”.
The character and sign which can be set up are the
same as C10.
[D43:CONV FACTOR] Conversion factor
Set the conversion factor when item D40 is “Yes(1)”
or “Special(2)”.
Set the conversion factor which is for both ow unit
and time unit in case of “Special(2)”.