Operation Manual

<6. PARAMETERS>
6-10
IM 01F06A00-01EN
(9) Item K : Maintenance
These items are for maintenance.
Item Name R / W Data Range Unit
Decimal
Point
Remark
Initial
Value
Disp. U / D
(*1)
K00 MAINTENANCE Menu K (Maintenance)
K10 TLA W 0.1 to 20.0 1 Trigger Level Adjust 1.0 D
K20 SIGNAL LEVEL W 0.1 to 20.0 1 Signal Level 1.0 D
K25 N.B. MODE W AUTO (0)
MANUAL (1)
TUNING AT ZERO (2)
Selection of Noise balance Mode (0) D
K26 NOISE RATIO R / W 0.00 to 2.00 2 D
K28 SET VORTEX F W 0 to 10000 Hz 0 to 5 Output test by setting simulated
frequency.
(*2)
D
K30 VELOCITY R m/s 2 Velocity D
K32 SPAN V R Hz 2 Span velocity D
K34 VORTEX FREQ. R Hz 0 to 5 Vortex frequency D
K36 SPAN F R 0 to 5 Span frequency D
(Indicate only for F10: Saturated Steam, Superheat Steam, LIQUID: Mass)
(*1)
K38 DENSITY R 0.00001 to 32000 D25 0 to 5 Density value (Calculated by
Thermometer)
D
K40
ERROR RECORD
R Error Records
K45 H VIBRATION W 0% (0)
NO ACTION (1)
Selection of Output Function when
“High Vibration” error is indicated.
(1)
(*3)
K50 SOFTWARE REV R 0.01 to 99.99 2 Software Revision Number
K60 SELF CHECK R GOOD
ERROR
Self-diagnostic message
/MV : Multi-Variable (Build-in Temperature Sensor) Type
(*1) : Available for 3.10 or greater version that can be checked in K50.
(*2) : Available for 5.10 or greater version that can be checked in K50.
(*3) : If 7.00 or less version that can be checked in K50, Initial Value is 0.
(10) Item M : Memo
These items are for Memorandum.
Item Name R / W Data Range Unit
Decimal
Point
Remark
Initial
Value
Disp. U / D
(*1)
M00 MEMO Menu M (Memo)
M10 MEMO 1 W 16 characters W Memorandum 1
(*2)
M20 MEMO 2 W 16 characters W Memorandum 2
(*2)
M30 MEMO 3 W 16 characters W Memorandum 3
(*2)
M60 SELF CHECK R GOOD
ERROR
R Self-diagnostic message
(*1) : Available for 3.10 or greater version that can be checked in K50.
(*2) : Available characters are same as C10.
Refer to Section 6.4 “Parameters Description.”