Operation Manual
    <6. PARAMETERS>
6-6
IM 01F06A00-01EN
(5)  Item E : Detector Setup
These items are for detector that has been already set before.
A value in “( )” is the data corresponding to the indicator.
Item Name R / W Data Range Unit
Decimal
Point
Remark
Initial
Value
Disp. U / D 
(*1)
E00 METER SETUP Menu E (Detector setup)
E10 NOMINAL SIZE W 15mm 
25mm 
40mm 
50mm 
80mm 
100mm 
150mm 
200mm 
250mm 
300mm 
400mm 
(0)
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
Selection of Nominal Size (1) 
(*2)
DL
E20 BODY TYPE W Standard 
High Pressure 
Low Flow Unit (1) 
Low Flow Unit (2) 
(0)
(1)
(2)
(3)
Selection of Body Type (0) D L
E30 SENSOR TYPE W Standard 
High Temperature 
Low Temperature 
(0)
(1)
(2)
Selection of Sensor Type (0) D L
E40 K-FACT UNIT W P/l 
P/USgal 
P/UKgal 
(0)
(1)
(2)
Selection of K-factor Unit (0) D L
E41 K-FACTOR W 0.00001 to 32000 E40 0 to 5 K-factor value of 15 deg C 68.6 D
E50 DETECTOR No. W 16 characters Detector number
E60 SELF CHECK R GOOD 
ERROR
Self-diagnostic message
FU : Flow unit
(*1) : Available for 3.10 or greater version that can be checked in K50.
(*2) : If specifi ed when ordering, it is set to the specifi ed contents.