Operation Manual
<6. PARAMETERS>
6-5
IM 01F06A00-01EN
(4) Item D : Additional Setup
These items are for Auxiliary Setup.
A value in “( )” is the data corresponding to the indicator.
Item Name R / W Data Range Unit
Decimal
Point
Remark
Initial
Value
Disp. U / D
(*1)
D00 AUX. SETUP Menu D (Additinal Setup)
D10 LOW CUT W * to 32000 FU + C40 0 to 5 Low Cut Flow rate
*Minimum Flow rate / 2
0.47 D
D20 TEMP UNIT W deg C
deg F
(0)
(1)
Selection of Temperature Unit (0)
(*2)
DL
D21 TEMP f W -999.9 to 999.9 D20 1 Operating Temperature (Manual
Setting Value)
15.0
(*2)
DL
D25 DENSITY UNIT W kg/m
3
lb/cf
lb/USgal
lb/UKgal
(0)
(1)
(2)
(3)
Selection of Density Unit (0)
(*2)
DL
D26 DENSITY f W 0.00001 to 32000 D25 0 to 5 Operating Density (Manual Setting
Value)
1024
(*2)
DL
D30 OUT LIMIT (H) W 100.0 to 110.0 % 1 Upper Limit Value 110.0 D L
D35 BURN OUT R High
Low
(0)
(1)
Output Direction at Burn Out (0) D L
D40 SPECIAL UNIT No
Yes
Special
(0)
(1)
(2)
Selection of change for Special Flow
Unit
(0) D L
(Indicate and Set only for D40: Yes, Special)
D41 BASE UNIT R m
3
k m
3
l
cf
m cf
k cf
USgal
kUSgal
UKgal
kUKgal
bbl
m bbl
k bbl
kg
t
lb
k lb
Nm
3
k Nm
3
M Nm
3
NI
Sm
3
k Sm
3
M Sm
3
SI
scf
k scf
M scf
(0)
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)
(12)
(13)
(14)
(15)
(16)
(17)
(18)
(19)
(20)
(21)
(22)
(23)
(24)
(25)
(26)
(27)
Basic unit for conversion to special
unit
N: Normal
S: Standard
D
(Indicate and Set only for D40: Yes, Special)
D42 USER’S UNIT W 8 characters User’s unit
(*3)
L
(Indicate and Set only for D40: Yes, Special)
D43 CONV
FACTOR
W 0.00001 to 32000 0 to 5 Conversion factor 1.0 D L
D60 SELF CHECK R GOOD
ERROR
Self-diagnostic message
FU : Flow unit
(*1) : Available for 3.10 or greater version that can be checked in K50.
(*2) : If specifi ed when ordering, it is set to the specifi ed contents.
(*3) : Available characters are same as C10.
Refer to Section 6.4 “Parameters Description.”