Operation Manual

<6. PARAMETERS>
6-4
IM 01F06A00-01EN
Item Name R / W Data Range Unit
Decimal
Point
Remark
Initial
Value
Disp. U / D
(*1)
C37 STD/NOR UNIT W Nm
3
k Nm
3
M Nm
3
Nl
Sm
3
k Sm
3
M Sm
3
Sl
scf
k scf
M scf
(0)
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
Selection of Volumetric Unit at
Normal
Condition
N: Normal
S: Standard
(0)
(*2)
DL
C40 TIME UNIT W /s
/m
/h
/d
(0)
(1)
(2)
(3)
Selection of Time Unit (2)
(*2)
DL
C45 FLOW SPAN W 0.00001 to 32000 FU+C40 0 to 5 Flow Span 10
(*2)
DL
C50 DAMPING W 0 to 99 sec 0 Damping Time 4 D L
C60 SELF CHECK R GOOD
ERROR
Self-diagnostic message
FU : Flow unit
(*1) : Available for 3.10 or greater version that can be checked in K50.
(*2) : If speci ed when ordering, it is set to the speci ed contents.