Operation Manual

<6. PARAMETERS>
6-2
IM 01F06A00-01EN
(1) Item A : Indication
These items are for the indication of owrate and total.
Item Name R / W Data Range Unit
Decimal
Point
Remark
Initial
Value
Disp. U / D
(*1)
A00 DISPLAY Menu A (Display)
A10 FLOW RATE (%) R 0.0 to 110.0 % 1 Flow rate
A20 FLOW RATE R 0.0 to 65535 FU+C40 0 to 5 Flow rate (in engineering unit)
A30 TOTAL R 0 to 999999
(*2)
FU 0 to 5 Totalized value
(Indicate only for /MV and B50 : TEMP)
A40 TEMP (%)
(*1)
R 0.0 to 110.0 % 1 Temperature Values (%)
(Indicate only for /MV)
A41 TEMPERATURE
(*1)
R –999.9 to 999.9 D20 1 Temperature Values
A60 SELF CHECK R GOOD
ERROR
Self-diagnostic message
FU : Flow unit
/MV : Multi-Variable (Build-in Temperature Sensor) Type
(*1) : Available for 3.10 or greater version that can be checked in K50.
(*2) : There will be linked to the value of B45, it is displayed “E” shows multipiler 10.
(2) Item B : Easy Setting
These items are for the principal items to operate digitalYEWFLO.
A value in “( )” is the data corresponding to the indicator.
Item Name R / W Data Range Unit
Decimal
Point
Remark
Initial
Value
Disp. U / D
(*1)
B00 EASY SETUP Menu B
B10 FLOW SPAN W 0.00001 to 32000 FU + C40 0 to 5 Flow Span 10 D L
B15 DAMPING W 0 to 99 sec 0 Damping Time 4 D L
B20 CONTACT OUT W OFF
SCALED PULSE
UNSCALED PULSE
FREQUENCY
ALARM
FLOW SW(LOW:ON)
FLOW SW(LOW:OFF)
(0)
(1)
(2)
(3)
(4)
(5)
(6)
Contact Output Type (0) D L
(Indicate and Set only for B20: SCALED PULSE, UNSCALED PULSE)
B21 PULSE RATE W 0.00001 to 32000 FU / P 0 to 5 Pulse Output Rate 1.0
(*3)
DL
(Indicate and Set only for B20: FREQUENCY)
B22 FREQ AT 100% W 0 to 10000 PPS 0 Pulse Output Rate at sec /100% 1000 D L
(Indicate and Set only for B20: FLOW SW (ON), FLOW SW (OFF))
B23 SET LEVEL W 0.00001 to 32000 FU +C40 0 to 5 Flow Switch (Actual Flow rate) 0 D L
B30 UPPER DISP W FLOW RATE (%)
FLOW RATE
TEMP (%)
(0)
(1)
(2)
Selection of Upper Display
(only for /MV)
(0)
(*3)
DL
B31 LOWER DISP W BLANK
TOTAL
TEMP
(0)
(1)
(2)
Selection of Lower Display
(only for /MV)
(0) D L
B40 TOTAL START W STOP
START
(0)
(1)
Start / Stop of Totalizer (0) D L
B45 TOTAL RATE W 0.00001 to 32000 (0) FU / P 0 to 5 Total Rate 1.0
(*3)
DL
B47 TOTAL RESET W NOT EXECUTE
EXECUTE
(0)
(1)
Totalizer Reset (0) D L
(Indicate and Set only for /MV)
B50 A / OUT SELECT W FLOW
TEMP
(0)
(1)
Selection of Analog Output (0) D L
(Indicate and Set only for /MV and B50: TEMP)
B51 TEMP 0% W -999.9 to 999.9 D20 1 Set Temperature Value at 0% -40 D L
B52 TEMP 100% W -999.9 to 999.9 D20 1 Set Temperature Value at 100% 250
(*2)
DL
B60 SELF CHECK R GOOD
ERROR
Self-diagnostic message
FU : Flow unit
(*1) : Available for 3.10 or greater version that can be checked in K50.
(*2) : If 7.00 or less version that can be checked in K50, Initial Value is 260.