Operation Manual

<5. BASIC OPERATING PROCEDURES>
5-7
IM 01F06A00-01EN
5.4.2 Data Setting Method
Input method of numeric data
Example 1: Change the span from 100m
3
/h to 150m
3
/h
The setting mode can be changed referring to Section 6.3 “Parameters List.”
SET
INCSHIFT
SET
INCSHIFT
SET
INCSHIFT
SET
INCSHIFT
SET
INCSHIFT
SET
INCSHIFT
SET
INCSHIFT
SET
INCSHIFT
F0508.ai
Press “ SET ” key.
Press “ SET ” key.
Press “ SHIFT ” key any time.
Press “ INC ” key any time.
Press “ SET ” key.
Press “ SET ” key.
Press “ SET ” and “ SHIFT ” key.
Indication of % flow
rate.
Enter to the setting
mode.
(Span number is
“ B10 ”)
Enter to data number
item.
Move the position to
input the data.
Set “ 5 ” and indicate
“ 150m
3
/h ”.
Ensure the setting
data.
Complete the Setting.
Return to display
mode.
IMPORTANT
After setting a parameter, keep the power on for
at least 30 seconds.
If the power of owmeter is turned off, a
parameter setting is released.