Operation Manual
    <5. BASIC OPERATING PROCEDURES>
5-2
IM 01F06A00-01EN
5.2 Display Contents
The display content items are classifi ed in the following three items.
Table 5.1  Mode Name List
Mode (status) Name Display Contents
Flow rate display mode A mode in which instantaneous fl ow rates or totalized values are displayed.
Display content is usually selected either in display content selection mode or by setting 
parameters via BRAIN communication.
Setting mode In this mode, parameter contents are confi rmed or data is updated using the setting section. The 
mode is changed to this mode when “SET” key is pressed in normal mode.
Alarm number display mode This mode is overlapped when an alarm is occurring in display mode. The alarm number 
presentation to indicate alarm contents (about 2 sec) and the normal data display (about 4 sec ) are 
repeated alternatively.
Mode represents that the system is in a state where the relevant setting or display is possible.
● Display Example
F0502.ai
SET
SHIFT 
+
 SET
Flowrate Display Mode Setting Mode Error Mode
UPPER 
Flow rate
LOWER 
Total rate
NORMAL 
INDICATION 
(4 sec)
ERROR INDICATION 
(2 sec)
UPPER 
Flow rate (%)
LOWER 
Blank
SHIFT
Alternately
This mode display can be selected 
below.
 Upper display : Flow rate
 Lower display : Total rate or Blank
 When an alarm situation occurs, 
this mode will replace the current 
mode (flow rate or setting mode) 
to show what type of alarm has 
occurred.
 Refer to Section 6.5 “Self- 
Diagnostic (Error Code List)” 
about the error descriptions and 
error number.
 This mode is used to check parameter 
content and rewrite data. This mode can 
be called up from the flowrate display 
mode by pressing the “SET” key.
 Setting item and setting number can be 
changed when pressing “SHFT” key.
 This mode can be called up by pressing 
“SET” key while pressing “SHIFT” key 
when setting mode is displayed.
Switching 
of setting 
number