Operation Manual
  <4. WIRING>
4-9
IM 01F06A00-01EN
(5) Perform attachment of fl ameproof packing 
adaptor in the following ways. Refer to Figure 
4.11.
(a) Loosen the locking screw and remove the 
terminal box cover.
(b)  Measure the cable outer diameter in two 
directions to within 0.1 mm.
(c)  Calculate the average of the two diameters, 
and use packing with an internal diameter 
nearest to this value. Refer to Table 4.2.
(d)  Screw the fl ameproof packing adapter into 
the terminal box until the O-Ring touches 
the wiring port (at least 6 full turns), and 
fi rmly tighten the lock nut.
(e)  Insert the cable through the union nut, the 
B. coupling, the clamp nut, the clamp ring, 
the packing gland, the washer, the packing, 
and the packing case, in that order.
(f)   Insert the end of the cable into the terminal 
box.
(g) Tighten the union cover to grip the cable. 
When tightening the union cover, tighten 
approximately one turn past the point where 
the cable will no longer move up and down.
Proper tightening is important. If it is too 
tight, a circuit break in the cable may 
occur; if not tight enough, the fl ameproof 
effectiveness will be compromised.
(h)  Fasten the cable by tightening the clamp 
nut.
(i)   Tighten the lock nut on the union nut.
(j)   Connect the cable wires to each terminal.
(6) 
(a)  Do not connect cables outdoors in wet 
weather in order to prevent damage from 
condensation and to protect the insulation.
(b)  Do not splice the cable between the 
fl owtube terminal and the converter if it is 
too short. Replace the short cable with a 
cable that is the appropriate length.
(c)  The signal cables must be routed in 
separate steel conduit tubes 16 (JIS C 
8305) or fl exible conduit tubes 15 (JIS C 
8309).
(d)  Always route the power and output signal 
cables in separate steel conduit tubes, 
except when the power supply voltage is 24 
V and four-core cables are used for wiring. 
Keep conduits or fl exible tubes watertight 
using sealing tape.
(7) For the TIIS fl ameproof type with wiring using 
a fl ameproof packing adapter, wire cables 
through the packing adapters approved by 
Yokogawa (option code: /G11 or /G12).
Unit : mm
(approx. inch)
F0414.ai
T1
T2
L
18
G
F
D
C
16.5
*Packing
(Choose from the table 
below depend on cable 
outside diameter)
Adapter body (M. Screw)
Packing case
Hexagon socket set screw
O-Ring
Packing *
O-Ring
O-Ring
Washer
Union nut
Packing gland
Clamp ring
Clamp nut
O-Ring
Hexagon socket set screw
B.coupling
Cable (user’s scope)
Size
Cable outer 
diameter
Packing 
dimensions
Identifi cation
mark
Weight 
kg (lb)
T1 T2 C D L F G
G 1/2 G 1/2
35 
(1.38)
39 
(1.54)
94.5 
(3.72)
ø8.0 to ø10.0
(ø0.31 to ø0.39)
ø10.0
(ø0.39)
ø20.0
(ø0.79)
16 8-10
0.26
(0.57)
ø10.0 to ø12.0
(ø0.39 to ø0.47)
ø12.0
(ø0.47)
16 10-12
Figure 4.12  Flameproof Packing Adapter (option 
code: /G11, /G12)
4.7 Grounding
IMPORTANT
When a lightning protector (option code: /A) is 
selected, use a grounding resistance of 10 or 
less.
(1) The grounding terminals 
 are located on the 
inside and outside of the terminal area. Either 
terminal may be used.
(2) For pulse output version, ground the fl owmeter. 
Also ground the shielded cable between the 
converter and the pulse receiver.
(3) Grounding should satisfy Class D requirements 
(ground resistance 100 or less).
(4)  Use 600V PVC insulated wire for grounding.
Example: Integral Type
Grounding 
Terminals
F0415.ai
Figure 4.13  Grounding Terminal