Operation Manual
    <3. INSTALLATION>
3-8
IM 01F06A00-01EN
Table 3.3 (a)  Installation of Wafer Type Vortex Flowmeter
Wafer type
Description
When Installation Collars are not required,the 
installation vortex flowmeters applied to the 
following line sizes and flanges. 
Size mm (inch) Flange Rating
50(2)
80(3)
100(4)
JIS 20K, 40K
ANSI class 300,600
JIS 10K, 20K, 40K
ANSI class 300, 600
JIS 10K, 20, 40K
ANSI class 150, 300, 600
Vertical InstallationHorizontal Installation
(1) Insert two stud bolts in the bolt holes
on the flowmeter shoulder to align 
the instrument body with the inner 
diameter of the adjacent piping.
(2) Tighten all bolts uniformly and check
that there is no leakage between the 
instrument and the flanges.
F0312.ai
Flow Direction
Nut
Nut
Gasket
Bolt Hole
Gasket
Flange
Flange
Flow
Direction
Stud Bolt (8 pcs.)
Electrical Connection
Electrical 
Connection
Electrical
Connection
Flange
Flow
Direction
Nut
Gasket
Collar (4 pcs.)
Collar (4 pcs.)
Gasket
Flange
Gasket
Gasket
Flange
Flange
Bolt (4 pcs.)
Bolt (4 pcs.)
Nut
Nut
Nut
Electrical
Connection
Flow Direction
Size mm (inch)
Flange Rating
15 to 40
(1/2 to 1-1/2)
50(2)
80(3)
All ratings
JIS 10K, ANSI class 150, 
DIN PN10 to PN40
ANSI class 150 
Vertical Installation
When Installation Collar are required, the 
installation vortex flowmeters applied to the 
following line sizes and flange ratings.
The inside diameter of the gasket must 
be larger than the pipe inner diameter 
so that it will not disturb the flow in the 
pipeline.
Horizontal Installation
When installing the Flowmeter vertically in the 
open air, change the electrical connection port 
direction to the ground. If the electrical 
connection port is installed upwards, rain 
water might leak in.
WARNING
In case of vertical installation, two collars in 
the upper part might move after the 
installation. But it doesn't influence the 
performance, please use the flowmeter under 
such condition.
WARNING
WARNING
(1) Insert two collars on each two bolts of bottom side of the flowmeter. 
(2) Fit the flowmeter body to the collars. And tighten the four bolts and nuts 
uniformly. 
(3) Check for leakage from the flange connections.