Operation Manual
    <14. EXPLOSION PROTECTED TYPE INSTRUMENT>
14-14
IM 01F06A00-01EN
Type “n” and Non-incendive
Hazardous Location Non Hazardous
Location
Class IIC, Zone 2, 
Class I, II,
Division 2,Groups A, B, C, D,
E, F and G, 
Class III, Division 1
[Integral type]
[Remote type]
DY (flowmeter)
SUPPLY
PULSE
+
+
–
+
–
+
–
+
–
+
–
Power
Supply
Receiver
DY (converter)
DY-N (flowmeter)
SUPPLY
PULSE
+
+
–
+
–
+
–
+
–
+
–
Power
Supply
Receiver
A
B
T
C
A
B
T
(*1)
DYC: Signal cable
(*1) Wire for T terminal
 With temperature sensor type : installed
 Without temperature sensor type: not installed
Non-incendive field wire parameters of vortex flowmeter (DY)
and vortex flow converter (DYA).
 Ui (Vmax)=30  Ii (Imax)=165mA  Pi (Pmax)=0.9W
 Ci=12nF  Li=0.15mH
Installation requirement between flowmeter, converter and
general purpose equirement.
 Uo  Ui Io  Ii Po  Pi Co  Ci+Ccable
 Lo  Li+Lcable
 Voc  Vmax Isc  Imax Ca  Ci+Ccable
 La  Li+Lcable
 Uo, Io, Po, Co Voc, Isc, Ca and La are nonincendive field
 wire parameters of general purpose equipment.
F1410.ai
General Purpose
Equipment
WARNING
•  The general purpose equipment must 
be CSA certifi ed as the equipment which 
have type n or non-incendive fi eld wire 
parameters.
•  Installation should be in accordance with 
Canadian Electrical Code Part I.
•  Dust-tight conduit seal must be used when 
installed in class II and III environments.
•  Do not alter drawing without authorization 
from CSA.
(6)  Dual Seal (Option code: /CF11, /CS11)
Dual Seal:
Certifi ed by CSA to the requirement of ANSI/ISA 
12.27.01
No additional sealing required.
Primary seal failure annunciation: at the O-ring seal 
portion between shedder bar and amplifi er housing.