    <14. EXPLOSION PROTECTED TYPE INSTRUMENT>
14-13
IM 01F06A00-01EN
(2) Wiring
• Explosion proof
WARNING
•  All wiring shall comply with Canadian 
Electrical Code Part I and Local Electrical 
Codes.
•  In Hazardous locations, wiring shall be in 
conduit as shown in the fi gure.
•  A SEAL SHALL BE INSTALLED WITHIN 
50cm OF THE ENCLOSURE.
•  When the equipment is installed in Division 
2, “FACTORY SEALED, CONDUIT SEAL 
NOT REQUIRED”.
(3) Operation
• Explosion proof
WARNING
•  Note a warning label worded as follows.
  Warning: OPEN CIRCUIT BEFORE 
 REMOVING COVER.
•  Take care not to generate mechanical 
spark when access to the instrument and 
peripheral devices in hazardous locations.
(4)  Maintenance and Repair
WARNING
•  The instrument modifi cation or part 
replacements by other than authorized 
representatives of Yokogawa Electric 
Corporation are prohibited and will void CSA 
Certifi cation.
(5)  Installation Diagram Intrinsically Safe 
(and Note)
Intrinsically safe
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
+
-
+
[Remote type]
DYA (converter)
SUPPLY
PULSE
A
B
T (*1)
C
A
B
T
DY
 (flowmeter)
SUPPLY
PULSE
Safety barriers
Safety barriers
[Integral type]
DY-N (flowmeter)
 Hazardous Location 
Group IIC, Zone 0
Class I, II, III, Division 1,
Groups A, B, C, D, E, F and G
Non Hazardous
 Location
DYC: Signal cable
(*1) Wire for T terminal
 With temperature sensor type : installed
 Without temperature sensor type: not installed
F1409.ai
Electrical parameters of vortex flowmeter (DY) and vortex flow
converter (DYA).
 Ui (Vmax)=30 V Ii (Imax)=165 mA Pi (Pmax)=0.9W
 Ci=12 nF   Li=0.15 mH
Installation requirements between flowmeter, converter and
Safety Barrier
 Uo  Ui Io  Ii Po  Pi Co  Ci+Ccable
 Lo  Li+Lcable
 Voc  Vmax Isc  Imax Ca  Ci+Ccable
 La  Li+Lcable
Uo, Io, Po, Co, Lo, Voc, Isc, Ca and La are parameters of
 barrier.
WARNING
•  In any safety barrier used output current 
must be limited by a resistor ‘R’ such that 
Io=Uo/R or Isc=Voc/R.
•  The safety barrier must be CSA certifi ed.
•  Input voltage of the safety barrier must be 
less than 250Vrms/Vdc.
•  Installation should be in accordance with 
Canadian Electrical Code Part I.
•  Dust-tight conduit seal must be used when 
installed in class II and III environments.
•  Do not alter drawing without authorization 
from CSA.