Operation Manual
    <14. EXPLOSION PROTECTED TYPE INSTRUMENT>
14-10
IM 01F06A00-01EN
Special conditions for safe use
•  Precautions shall be taken to minimize the risk 
from electrostatic discharge of painted parts.
•  When the enclosure of the fl ow meter or the 
fl ow converter are made of aluminum, if it is 
mounted in an area where the use of EPL Ga 
equipment is required, it must be installed such 
that, even in the event of rare incidents, ignition 
sources due to impact and friction sparks are 
excluded.
•  The dielectric strength of at least 500 V a.c. 
r.m.s. between the intrinsically safe circuits and 
the enclosure of the fl ow meter or the converter 
is limited only by the overvoltage protection.
(2) Installation
WARNING
•  All wiring shall comply with local installation 
requirements and local electrical code.
•  Use the suitable heat-resisting cables (over 
90°C) for the digitalYEWFLO Model DY 
Series Vortex Flowmeter when the ambient 
temperature exceeds 60°C and/or the 
process temperature exceeds 200°C.
•  Cable gland and adapters shall be of Ex “d” 
for Ex “d” installations.
•  Cable gland and adapters shall be installed 
so as to maintain the specifi ed degree of 
protection (IP Code) of the fl owmeter.
The grounding terminals are located on the inside 
and outside of the terminal area.
Connect the cable to grounding terminal in 
accordance with wiring procedure (1) or (2).
Case
Cable
Screw
(1) Internal grounding terminal (2) External grounding terminal
Washer
Washer
Cable
Clamp
Screw
F1406.ai
Figure 14.2  Wiring Procedure for Grounding 
Terminals
(3) Operation
WARNING
•  Wait 3 min. after power is turned off, before 
opening the covers.
•  Take care not to generate mechanical 
spark when access to the instrument and 
peripheral devices in hazardous locations.
(4)  Maintenance and Repair
WARNING
•  The instrument modifi cation or parts 
replacement by other than authorized 
representative of Yokogawa Electric 
Corporation is prohibited and will void the 
certifi cation.