Operation Manual
<13. GENERAL SPECIFICATIONS>
13-20
IM 01F06A00-01EN
13.6 Option Specifi cations (For Explosion Protected Type)
* Refer to “Contact rating” for the maximum current value of Pulse Circuit.
Item Specifi cation Code
TIIS Certifi cation TIIS Flameproof Approval (Note 1)
Flameproof Ex d IIC T6 Certifi ed by TIIS.
(TIIS is the abbreviation of Technology Institution of Industrial Safety.)
Amb. Temp: –20 to 60°C
Electrical connection: JIS G1/2 female
JF3
Factory Mutual
(FM)
FM Explosion proof Approval
Applicable Standard: FM3600, FM3611, FM3615, FM3810, ANSI/NEMA 250
Type of Protection: Explosion proof for Class I, Division 1, Groups A, B, C and D;
Dust-ignitionproof Class II/III, Division 1, Groups E, F, and G.
“SEAL ALL CONDUITS WITHIN 18 INCHES.” “WHEN INSTALLED IN DIV.2, SEALS NOT REQUIRED.”
Enclosure Rating: Type 4X
Temperature Code: T6
Ambient Temperature: –29 to 60°C (Integral Type Vortex Flowmeter and Remote Type Vortex Flow Detector)
–40 to 60°C (Remote Type Vortex Flow Converter)
Ambient Humidity: 0 to100%RH (No condensation)
Coating of Enclosure: Epoxy resin coating or Polyurethane resin coating.
Electrical Connection: ANSI 1/2NPT female
FF1
FM Intrinsically safe Approval (Note 2)
Applicable Standard: FM3600, FM3610, FM3611, FM3810, NEMA-250, ANSI/ISA-60079-0, ANSI/ISA 60079-11
Type of Protection: Intrinsically safe:
Class I, Division 1, Groups A, B, C and D, T4
Class II, Division 1, Groups E, F and G, T4
Class III, Division 1, T4
Class I, Zone 0, AEx ia IIC T4
Nonincendive:
Class I, Division 2, Groups A, B, C and D, T4
Class II, Division 2, Groups F and G, T4
Class III, Division 1, T4
Ambient Temperature: –29 to +60°C (Integral Type Vortex Flowmeter)
–29 to +80°C (Remote Type Vortex Flow Detector)
–40 to +60°C (Remote Type Vortex Flow Converter)
Ambient Humidity: 0 to 100% RH (No condensation)
Indoors and Outdoors: Type 4X
Electrical Parameter: Vmax=30Vdc, Imax=165mAdc, Pi=0.9W, Ci=12nF, Li=0.15mH
Electrical Connection: ANSI 1/2NPT female
FS1
ATEX ATEX Flameproof Approval (Note 3)
Applicable Standard: EN 60079-0, EN 60079-1
Type of Protection: II2 G Ex d IIC T6...1 Gb (Integral Type Vortex Flowmeter and Remote Type Vortex Flow Detector)
II2 G Ex d IIC T6 Gb (Remote Type Vortex Flow Converter)
Groups: II, Category: 2 G
Temperature Class: T6...T1 (Integral Type Vortex Flowmeter and Remote Type Vortex Flow Detector)
T6 (Remote Type Vortex Flow Converter)
Process Temp.: T6 (-29 to 80°C), T5 (-29 to 100°C), T4 (-29 to 135°C),
T3 (–29 to 200°C), T2 (–29 to 300°C) T1 (–29 to 450°C)
(Use /HT version above 250°C),
Ambient temperature: –29 to 60°C (Integral Type Vortex Flowmeter and Remote Type Vortex Flow Detector)
–40 to 60°C (Remote Type Vortex Flow Converter without indicator)
–30 to 60°C (Remote Type Vortex Flow Converter with indicator)
Ambient Humidity: 0 to 100%RH (No condensation)
Electrical Connection: ANSI 1/2NPT female, ISO M20 × 1.5 female
KF2
ATEX Intrinsically Sare (Note 2)
Applicable Standard: EN 60079-0, EN 60079-11, EN 60079-26
Type of protection: Ex ia IIC T4...T1Ga (Integral Type Vortex Flowmeter)
Ex ia IIC T6...T1 Ga (Remote Type Vortex Flow Detector)
Ex ia IIC T4 Ga (Remote Type Vortex Flow Converter)
Groups/Category: II 1 G
Temperature Class: T4...T1(Integral Type Vortex Flowmeter)
T6...T1(Remote Type Vortex Flow Detector)
T4 (Remote Type Vortex Flow Converter)
Ambient temperature: –29 to +60°C (Integral Type Vortex Flowmeter)
–40 to +80[79]°C (Remote Type Vortex Flow Detector)
(Option /LT below –29°C, [ ] for Option /MV at T6)
–40 to +80°C (Remote Type Vortex Flow Converter without indicator):
–30 to +80°C (Remote Type Vortex Flow Converter with indicator):
Ambient Humidity: 5 to 100%RH (No condensation)
Process temperature: T6: –196 to 84[79]°C, T5: –196 to 100°C, T4: –196 to 135°C,
T3: –196 to 199°C, T2: –196 to 299[289]°C, T1: –196 to 449[439]°C
(Option /HT above 250°C and Option /LT below -29°C, [ ] : Option /MV)
Signal/Supply (Terminals SUPPLY + and –) and Pulse (Terminals PULSE + and –) Circuit:
Ui = 30 V, Ii = 300 mA, Pi = 0.9 W (linear source), Ci = 14 nF, Li = 0 mH
Electrical connection: ANSI 1/2 NPT female, ISO M20 × 1.5 female
KS2
(Note 1) The fl ameproof packing adapter /G11 or /G12 is necessary except the electrical conduit work. In case the ambient
temperature exceeds 50°C, use heat resistant cables with maximum allowable temperature of 70°C or above.
(Note 2) For intrinsically safe approval, use the barrier certifi ed by the testing laboratories (BARD-400 is not applicable).
(Note 3) Cryogenic Version /LT is not available.