Operation Manual
    <9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>
9-12
IM 01F06A00-01EN
(3) Squawk (Effective only when setting to 
HART 7)
This feature can be used to identify the 
communicating device by remotely causing LCD to 
display the particular pattern as shown in the Figure 
9.4
“SQUAWK” continues for approximately 10 
seconds, then is released automatically.
•  Procedure to call up the Squawk display
[Root Menu]  Diag/Service  Squawk(Method)
F0908.ai
Figure 9.4  Display for Squawk
9.10.6  Switching HART Protocol Revision
When the output signal code is “-J”, HART protocol 
revision of the device can be selectable from 5 or 7.
The HART protocol revision is set and shipped as 
specifi ed in the order.
To change the HART protocol revision after 
shipment, follow the procedure shown below.
IMPORTANT
When change the protocol revision, confi rm the 
items below.
•  Protocol revision supported by HART 
confi guration tool must be the same or 
higher than new protocol revision of the 
device. (Refer to Section 9.1 “HART Protocol 
Revision”)
• Confi rm that the DD or DTM which is suitable 
to new protocol revision of the device is 
installed in the confi guration tool. (Refer to 
Section 9.2 “HART Confi guration Tool and 
Matching of Device Revision” and Section 
9.3 “Setting Parameters using DTM”)
(1) Call up the parameter for protocol revision 
change
•  Procedure to call up the Chng universal rev 
display.
DD (HART 5/7)
DTM (HART 7)
[Root Menu]  Detailed setup  
Device information  Revision numbers 
Chng universal rev
DTM (HART 5) [Root Menu]  Confi guration  
HART  Chng universal rev
(2)  Activate the “Chng universal rev” method
IMPORTANT
The message is displayed to separate the device 
from the automatic control loop.
Confi rm that the device is separated.
(3)  Input the new revision number
An input column for new protocol revision number 
is displayed. Input the new HART protocol revision 
number of “5” for HART 5 or “7” for HART 7.
It checks that the revision number which it is going 
to change into the Next universal rev column is 
displayed. 
[Root Menu]  Detailed setup  Device 
information  Revision numbers  Next universal 
rev
(4)  Applying the new protocol revision
a. Close the confi guration tool
  After completion of Chng universal rev 
method, close the HART confi guration tool.
NOTE
When using a FieldMate, close the main display 
of FieldMate.
b. Restart the device
  Turn off the power to the device, and turn it 
on.
IMPORTANT
New protocol revision is applied only after having 
performed restart of the device.