Operation Manual
    <9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>
9-2
IM 01F06A00-01EN
9.4 Interconnection between 
digitalYEWFLO and HART 
Confi guration Tool
The HART Confi guration Tool can interface with 
the digitalYEWFLO from the control room, the 
digitalYEWFLO site, or any other wiring termination 
point in the loop, provided there is a minimum load 
resistance of 250  between the connection and 
the receiving instrument. To communicate, it must 
be connected in parallel with the digitalYEWFLO, 
and the connections must be non-polarized. Figure 
9.2 illustrates the wiring connections for a direct 
interface at the digitalYEWFLO site. The HART 
Confi guration Tool can be used for remote access 
from any terminal strip as well.
+
–
4 to 20 mA DC signal line
Control room
Terminal board
Receiving instrument
load resistance:
 250  to 600 
Relaying
terminals
HART
Configuration Tool
HART
Configuration Tool
HART
Configuration Tool
F0903.ai
digitalYEWFLO
SUPPLY
SUPPLY
+
–
Figure 9.2  Connecting the HART Communicator
WARNING
Be sure to set parameters as “Protect” on the 
write protect function after fi nish of parameter 
setting work.
Refer to Section 9.9 “Software Write Protect” 
how to use the write protect function in detail.
IMPORTANT
If the power of fl owmeter is turned off within 30 
seconds after parameters have been set, these 
settings will be canceled. Accordingly, please 
keep the power on for at least 30 seconds after 
setting parameters.
NOTE
Before updating any setting, remember to 
always check the data content you want to 
change as described in Section 6.4 “Parameters 
Description”.
9.5 Basic Setup
 Tag and Device Information
The tag number and device information can be 
checked as follows:
•  Procedure to call up the tag number and device 
information
Tag [Root Menu] → Basic setup → Tag
or [Root Menu] → Detailed setup
→ Device information → Tag
or  [Root Menu] → Review → Review1 → Tag
Long Tag [Root Menu] → Basic setup → Long Tag
or  [Root Menu] → Detailed setup
→ Device information → Long Tag
or  [Root Menu] → Review → Review1 
→ Long Tag
Descriptor or [Root Menu] → Detailed setup
→ Device information → Descriptor
or  [Root Menu] → Review → Review1 
→ Descriptor
Message or  [Root Menu] → Detailed setup
→ Device information → Message
or  [Root Menu] → Review → Review1 
→ Message
Date or  [Root Menu] → Detailed setup
→ Device information → Date
or  [Root Menu] → Review → Review1 → Date
When changing the tag number or device 
information, enter the information directly within the 
following limitations.
Item Limitations
Tag Up to 8 characters or numbers
*1
Long Tag
(HART 7 only)
Up to 32 characters or numbers
*2
Descriptor Up to 16 characters or numbers
*1
Message Up to 32 characters or numbers
*1
Date yyyy/mm/dd
- mm : month (2 digits)
- dd : days (2 digits)
- yy : years (2 digits)
SPACE
 ! " # $ % & ' ( ) * + , - . /
 0   1   2  3   4   5   6   7   8   9  :  ;  <  =  >   ?
@  A  B C D E F G H  I  J K L M N O
 P Q R S T U V W X Y Z [ \ ] ^ _
 `  a  b  c  d  e  f  g  h  i  j  k  l  m  n  o
 p  q  r  s  t  u  v  w  x  y  z  {  |  }  ~ 
F0904.ai
*1: The characters bounded by the thick line in the following 
  table can be used. 
*2: All characters in the following table can be used.