Operation Manual
    <8. OPERATION VIA HART CONFIGURATION TOOL (HART 5)>
8-4
IM 01F06A00-01EN
8.10.2 Multidrop Mode
“Multidropping” devices refers to the connection 
of several devices to a single communications 
transmission line. Up to 15 devices can be 
connected when set in the multidrop mode. To 
activate multidrop communication, the device 
address must be changed to a number from 1 to 
15. This change deactivates the 4 to 20 mA analog 
output, sending it to 4 mA. The alarm current is also 
disabled.
(1) Polling address
•  Procedure to call up the display
DD (HART 5) [Root Menu]  Detailed setup 
Confi gure outputs  HART output 
DTM (HART 5) Confi guration  HART 
 Poll addr Enter the number from 1 to 15
(2)  Enabling the Multidrop Mode
About the procedure to call up the Polling 
display, please refer to the User’s Manual of 
each confi guration tool.
NOTE
When the same polling address is set for two or 
more devices in multidrop mode, communication 
with these devices are disabled.
(3)  Communication when set in multidrop mode.
•  The HART confi guration tool seaches for a 
device that is set in multidrop mode when it is 
turned on. When the HART confi guration tool 
is connected to the device, the polling address 
andthe tag will be displayed.
•  Select the desired device. After that, normal 
communication to the selected device is 
possible. However, the communication speed 
will be slow.
To release multidrop mode, call up the Poll addr 
display and the address to “0”.
8.10.3  Switching HART Protocol Revision
When the output signal code is “-J”, HART protocol 
revision of device can be selectable from 5 or 7.
The HART protocol revision is set and shipped as 
specifi ed in the order.
To change the HART protocol revision after 
shipment, follow the procedure shown below.
IMPORTANT
When change the protocol revision, confi rm the 
items below.
•  Protocol revision supported by HART 
confi guration tool must be the same or 
higher than new protocol revision of the 
device. (Refer to Section 8.1 “HART Protocol 
Revision”)
• Confi rm that the DD or DTM which is suitable 
to new protocol revision of device is installed 
in the confi guration tool. (Refer to Section 
8.1 “HART Protocol Revision” and Section 
8.2 “HART Confi guration Tool and Matching 
of Device Revision”)
(1)  Call up the parameter for protocol 
revision change
•  Call up the parameter for protocol revision 
change Procedure to call up the Chng 
universal rev display.
  [Root Menu]  Detailed setup  Device 
information  Revision numbers  Chng 
universal rev
(2)  Active the parameter for protocol 
revision change
•  Active the “Chng universal rev” method
IMPORTANT
The message is displayed to separate the device 
from the automatic control loop.
Confi rm that the device is separated.
(3)  Set the protocol revision number
Input the new revision number
An input column for new protocol revision 
number is displayed.
Input the new HART protocol revision number 
of “5” for HART 5 or “7” for HART 7.
Confi rm the revision number in the ‘Next 
universal rev’.
[Root Menu]  Detailed setup  Device 
information  Revision numbers  Next 
universal rev
(4)  Applying the new protocol revision
a. Close the confi guration tool
  After completion of Chng universal rev 
method, close the HART confi guration tool.