Operation Manual
    <7. OPERATION FOR THE BRAIN TERMINAL (BT200)>
7-1
IM 01F06A00-01EN
7.  OPERATION FOR THE BRAIN 
TERMINAL (BT200)
This chapter describes the operation procedures 
using a BRAIN TERMINAL (BT200). For details 
on the functions of the digitalYEWFLO, refer to 
Chapter 6 “PARAMETERS.” List. And also, refer to 
the “Model BT200 BRAIN TERMINAL” Instruction 
Manual (IM 01C00A11-01E) for more detailed 
Information.
7.1  Connection Method for the 
BT200
(1)  Connecting the BT200 to a 4 to 20mA 
DC Transfer Line
  The communication signal of the 
digitalYEWFLO is superimposed onto the 4 to 
20mA DC analog signal to be transferred.
digitalYEWFLO
SUPPLY
BT200 BT200 BT200 BT200
Inter mediate 
terminals
4 to 20mA DC 
Signal 
transmission 
line
Control room
Receiving 
instrument
load 
resistance:
WR
Terminal 
Board
SUPPLY
F0701.ai
Figure 7.1  Communicating for a 4 to 20mA DC 
Signal Line
IMPORTANT
The communicable distance of the transmission 
line is restricted depending on the wiring method. 
Refer to Chapter 4 “WIRING.” 
IMPORTANT
After setting a parameter, keep the power on for 
at least 30 seconds.
If the power of fl owmeter is turned off, a 
parameter setting is released.
(2)  Connection of BT200 to Flow Converter
  Removing a cover and indicator, the terminals 
for BRAIN communication are provided on the 
circuit board.
  Connect BT200 to the terminal of HHT-COM on 
the circuit board.
TP2
COM
HHT
P
F0702.ai
BT200
Display
Indicator Mounting 
Screw (2 PCS)
Circuit board
Figure 7.2  Connection of BT200 to Flow Converter